cmr-780-18.00•780 CMR 18.00 — Chapter 18: Chimneys and Vents Amendments
780 CMR 18.00 — Chapter 18: Chimneys and Vents Amendments
cmr-780-18.00780 CMR 18.00Regulation
18.00 Chapter 18: Chimneys and Vents Amendments
THIS IS AN UNOFFICIAL COPY OF THE REGULATIONS – OFFICIAL COPIES MUST BE OBTAINED FROM THE SECRETARY OF THE COMMONWEALTH
780 CMR: MASSACHUSETTS AMENDMENTS TO THE INTERNATIONAL BUILDING CODE 2021
780 CMR 51.00: MASSACHUSETTS RESIDENTIAL CODE (Amendments to the 2021 International Residential Code)
CHAPTER R18 CHIMNEYS AND VENTS Revise and replace section M1801.1 Venting required as follows: M1801.1 Venting required. Fuel-burning appliances shall be vented to the outdoors in accordance with their listing and label and manufacturer’s installation instructions except appliances listed and labeled for unvented use. Venting systems shall consist of approved chimneys or vents, or venting assemblies that are integral parts of labeled appliances. Add an Exception after M1801.11 Multiple-appliance venting systems Item #1 as follows: Item #1 - EXCEPTION: Engineered systems as provided for in Section G2427. Add an Exception to section M1801.12 Multiple solid fuel prohibited as follows: EXCEPTION: Unless common connection is allowed by 248 CMR or 527 CMR. If allowed, the common flue shall be of such size to serve all appliances connected if such appliances were operated simultaneously. Note that 248 CMR and 527 CMR are enforced by gas inspectors and the heads of fire departments, respectively.