TITLE 	11
DEPARTMENT 	OF 	HEALTH
CHAPTER 	39
AIR CONDITIONING AND VENTILATING
Purpose
Definitions
References
General 	requirement
Exemptions
Permit
Design 	conditions
Outdoor 	air 	supply
§11-39-2
Air movement, 	distribution, 	recirculation,
and 	removal
Hospitals 	and medical 	facilities
Air 	filtration 	apparatus
Systems 	for 	ventilating 	only
Garage 	ventilation
Right 	to 	inspect
Variation
Penalty 	for 	violation
Severability
Historical 	Note: 	Chapter 	39 	of 	Title 	11, 	Adminis-
trative 	Rules, 	is 	based 	substantially on 	Public 	Health
Regulations 	Chapter 	28, 	Air 	Conditioning 	and 	Ventilating,
Department 	of 	Health, 	State 	of 	Hawaii. 	[Eff. 	7/1/53,
am 	5 / 6 / 6 4 , 	am 	8 / 17/64 ; 	R 	J A N 3 1 19 83
§11-39-1 	Purpose. 	These 	rules 	are 	adopted 	under
chapter 	91, 	HRS 	and 	implements 	section 	321-11(13), 	HRS
and 	the 	following 	objectives:
(1) 	Seek 	to 	assure 	the 	adequate 	and 	healthful
design, 	construction, 	installation, 	and
operation of 	comfort 	air 	conditioning 	and
ventilating 	systems.
(2) 	Provide minimum ventilation 	requirements.
[Eff. 	JAN 3 1 1983 	] 	(Auth: 	HRS 	§§321-9,
321-11) 	(Imp: 	HRS 	§§321-1, 	321-11)
§11-39-2 	Definitions. 	As 	used 	in 	this 	chapter:
"Designer" 	means 	a 	registered 	architect 	or 	a
professional 	engineer 	especially 	qualified 	in 	the
mechanical 	branch.
"Department" 	means 	the 	department 	of 	health of 	the
39-1
§11-39-2
--------&eaee-e~-&awa±~·-.--------------------------------;--'~
"Director" 	means 	the 	director 	of 	the 	department 	of
health or 	a 	duly 	authorized 	agent 	or 	representative.
"Mechanical 	branch" 	means 	one 	of 	seven 	specialties
in 	the 	field 	of 	engineering 	in which 	a 	professional
license 	is 	issued 	under 	chapter 	464, 	HRS, 	and 	chapter
147, 	Title 	12, 	Administrative 	Rules 	of 	the 	Board of
Professional 	Engineers, 	Architects, 	Surveyors, 	and
Landscape 	Architects. 	Refer 	to 	chapter 	147, 	Title 	12
for 	list 	of 	specialties.
"Permit" 	means 	a 	permit 	issued 	to 	a 	designer 	under
this 	chapter.
"Public 	buildings" 	mean 	any 	structure 	used 	in
whole 	or 	in 	part 	as 	a 	place 	or 	resort, 	assemblage,
lodging, 	business, 	industry, 	trade, 	traffic, 	occupancy
or 	use 	by 	the 	public 	or 	by 	a 	segment 	of 	the 	public, 	or
by 	three 	or more 	tenants.
"Seal" 	means 	an 	identification 	stamp 	as 	an 	evidence
of 	registration 	as 	a 	professional 	architect or 	pro-
fessional 	engineer 	especially 	qualified 	in 	the
mechanical 	branch 	by 	the 	State 	of 	Hawaii.
All 	technical 	definitions 	for 	this 	rule 	shall 	be
governed 	by 	the 	American 	Society of 	Heating, 	Refrigera-
ting, 	and 	Air-Conditioning 	Engineers' 	Handbooks:
Fundamentals, 	Equipment, 	Systems, 	and Applications.
[Eff. 	JAN 3 1 1983 	] 	(Auth: 	HRS 	§§321-9, 	321-11)
(Imp: 	HRS 	§§321-1, 	321-11)
§11-39-3 	References. 	The 	following 	references
shall 	be 	used 	as 	a 	guide 	for 	good 	engineering 	practice:
(1) 	Handbooks 	of 	the ASHRAE 	(American 	Society of
Heating, 	Refrigerating 	and Air-conditioning
Engineers): 	Fundamentals 	(1981 	edition),
Equipment 	(1979 	edition), 	Systems 	(1980
edition), 	and 	Applications 	(1982 	edition).
(2) 	Safety 	Code 	for 	Mechanical 	Refrigeration,
American 	National 	Standards 	Institute 	(ANSI)
Standard ANSI/ASHRAE 	15, 	1978 	edition.
(3) 	Industrial 	Ventilation 	- 	Manual 	of 	Recommended
Practice 	American 	Conference 	of 	Government
Industrial 	Hygienists, 	1980 	edition.
(4) 	Standard 	for 	Ventilation 	for 	Acceptable
Indoor 	Air 	Quality. 	ASHRAE 	Standard 	62,
1981 	edition.
(5) 	Thermal 	Environmental 	Conditions 	for 	Human
Comfort. 	ASHRAE 	Standard 	55, 	1981 	edition.
(6) 	NFPA 	(National 	Fire 	Protection Association)
Standard 	90A. 	Standard 	for 	the 	Installation
of 	Air 	Conditioning 	and Ventilating 	Systems,
1978 	edition.
(7) 	NFPA 	Standard 	96. 	Removal 	of 	Smoke 	and
Grease-Laden 	Vapors 	from 	Commercial 	Cooking
39-2
§11-39-4
Equipment, 	1980 	edition.
(8) 	SMACNA 	(Sheet Metal 	& Air 	Conditioning Con-
tractors' 	National 	Association) 	low pressure
duct 	construction 	standards, 	1976 	edition.
[Eff. 	JAN311983 	] 	(Auth: 	HRS§§321-9,
3 21-11 ) 	( Imp : 	HRS 	§ § 3 21-1 , 	3 21-11 )
§11-39-4 	General 	requirements. 	The 	provisions 	of
these 	rules 	apply when 	a 	comfort 	air 	conditioning
system or 	a 	ventilating 	system 	is 	to 	be 	installed 	in
buildings 	used 	or 	to 	be 	used 	as 	public 	buildings.
(1) 	New buildings. 	These 	rules 	apply 	to 	all 	new
buildings. 	New buildings 	mean 	buildings,
additions 	thereto 	and 	alterations 	thereof,
for 	which 	plans 	have 	not 	been 	approved 	by 	the
department 	previously 	or 	construction was 	not
in 	progress 	prior 	to 	the 	effective 	date 	of
these 	rules.
(2) 	Existing 	buildings. 	These 	rules 	apply 	to 	all
alterations 	or 	improvements 	to 	existing
buildings, 	including 	the 	replacement 	of 	any
major 	apparatus 	or 	device 	related 	to 	air
conditioning 	or 	ventilating 	systems. 	Existing
buildings mean 	buildings, 	additions 	thereto
and 	alterations 	thereof, 	structurally 	com-
pleted 	or 	for 	which 	plans 	have 	been 	approved
by 	the 	department 	and 	construction 	is 	in
progress 	prior 	to 	the 	effective 	date 	of 	these
rules.
(3) 	Change 	in 	use. 	These 	rules 	apply 	to 	every
building, 	or 	portion 	of 	a 	building, 	devoted
to 	new use 	for 	which 	the 	requirements 	under
these 	rules 	are 	more 	stringent 	than 	the
requirements 	covering 	the 	previous 	use.
(4) 	Design 	and 	preparation of 	plans. 	All 	plans
and 	data 	on 	air 	conditioning 	and 	ventilating
systems 	shall 	be 	prepared by 	or 	under 	the
direct 	supervision 	of 	a 	"designer." 	All 	air
conditioning 	insta1lations 	shall 	be 	designed
and 	installed 	to 	provide 	proper 	comfort 	as
defined 	in ASHRAE 	Standard 	55, 	unless 	con-
strained 	by 	laws 	of 	the 	United 	States 	of
America 	or 	the 	State 	of 	Hawaii 	for 	reasons 	of
conservation 	of 	energy.
(5) 	Refrigeration 	system. 	The 	entire 	installation
of 	refrigeration 	in 	connection with 	air
conditioning 	shall 	be 	in 	accordance 	with good
engineering 	practice 	and 	the 	provisions 	of
ANSI/ASHRAE 	15.
(6) 	User's 	responsibility. 	All 	users 	shall
maintain 	air 	conditioning 	and 	ventilating
systems 	in 	good 	working 	order 	and 	shall
39-3
7 8
§11-39-4
_____________ope:r:a-t.e~t.hem--se-a-s--to-prov±d~e-a-ccepEab7:e
atmospheric 	conditions 	in 	the 	enclosure
during 	all 	periods 	of 	occupancy.
(7) 	Provisions 	for 	cleanliness. 	All 	parts 	of
installations 	and 	equipment which 	house 	or
handle 	air 	used 	for 	ventilating 	purposes
shall 	be 	designed 	so 	as 	to 	facilitate 	sanitary
maintenance 	thereof. 	[Eff. 	JAN 3 1 1983 	]
(Auth: 	HRS 	§§321-9, 	321-11) 	(Imp: 	HRS
§§321-1, 	321-11)
§11-39-5 	Exemptions. 	These 	rules 	do 	not 	apply 	to
the 	types 	of 	systems 	named 	below.
(1) 	Units 	of 	four 	and 	one-fourth 	tons 	refrigeration
(fifteen 	kilowatt) 	cooling 	capacity 	or 	less
are 	exempt 	from 	§11-39-6 	provided 	that 	they
are 	not 	part 	of 	a 	multiple 	installation, 	with
a 	combined 	capacity 	greater 	than 	four 	and
one-fourth 	tons 	(fifteen 	kilowatt) 	furnished
to 	ventilate 	any 	room 	or 	similar 	single
enclosure; 	all 	other 	sections 	of 	this 	rule
shall 	remain 	applicable 	to 	units 	of 	four 	and
one-fourth 	tons 	(fifteen 	kilowatt) 	or 	less.
(2) 	Ventilating 	systems 	including 	multiple
installation with 	a 	total 	of 	two 	thousand one
hundred 	cubic 	feet 	per minute 	(one 	thousand
litres 	per 	sec) 	capacity 	or 	less 	are 	governed
by 	these 	rules 	but 	no 	permit 	is 	required.
[Eff. 	JAN311983 	] 	(Auth: 	HRS 	§§321-9,
3 21-11 ) 	( Imp : 	HRS 	§ § 3 21-1 , 	3 21-11 )
§11-39-6 	Permit. 	(a) 	No 	person 	shall 	install,
alter, 	or 	operate 	an 	air 	conditioning 	or ventilating
system without 	first 	obtaining 	from 	the 	department 	a
valid 	permit 	covering 	the 	specific 	installation, 	altera-
tion, 	or 	operation.
(b) 	Form 1, 	Application 	for 	Permit, 	dated 	July
1981, 	located 	at 	the 	end 	of 	this 	chapter 	shall 	be 	used
as 	a 	permit 	application 	form 	and 	permit.
(c) 	Revocation, 	suspension, 	or 	denial 	of 	permit.
The 	department may 	on 	its 	own motion, 	or 	on 	the 	complaint
of 	any 	person, 	revoke, 	suspend, 	or 	deny 	a 	permit 	after
notifying 	the 	permittee 	or 	applicant 	and 	offering 	him
an 	opportunity 	to 	be 	heard. 	Revocation, 	suspension, 	or
denial 	of 	a 	permit 	shall 	be 	grounded on 	a 	violation 	of
this 	chapter. 	[Eff. 	JAN 3 1 1983 	] 	(Auth: 	HRS
§§321-9, 	321-11) 	(Imp: 	HRS 	§~321-1, 	321-11)
§11-39-7 	Design 	conditions. 	(a) 	Outside 	and
inside 	design 	conditions. 	The 	following 	design 	condi-
39-4
§11-39-8
tions 	shall 	be 	used 	for 	air 	conditioning 	systems which
will 	be 	operated 	at 	near maximum 	load 	in 	daylight
hours, 	at 	elevations 	below three 	thousand 	two 	hundred
eighty-one 	feet 	(one 	thousand metres) 	above 	sea 	level:
OUTSIDE 	INSIDE
Dry 	Bulb
87°F 	(30.6°C)
or 	higher
Wet 	Bulb
75°F 	(23.9°C)
or 	higher
Dry Bulb
78°F 	(25.6°C)
or 	lower
Relative
Humidity
60%
or 	lower
By 	special 	application 	to 	the 	director 	the 	above 	condi-
tions may 	be modified 	for 	systems 	whose 	loads 	peak 	at
times 	when 	outdoor 	temperature 	is 	much 	lower 	than 	daily
maximum or 	systems 	at 	higher 	altitudes, 	and 	in 	this
case 	design 	condition 	shall 	be 	as 	agreed 	between 	the
designer 	and 	the 	director.
(b) 	Design 	cooling 	load. 	Minimum allowances 	to
be made 	in 	estimating 	the 	net 	instantaneous 	heat 	gains
in 	a 	building 	shall 	be 	in 	accordance 	with 	good
engineering 	practice.
(c) 	Infiltration. 	Infiltration 	air 	volume 	rate
and 	the 	sensible 	and 	latent 	heat 	gains 	therefrom 	shall
be 	determined 	for 	air 	conditioning 	systems; 	and where
calculated 	infiltration 	rate 	differs 	from 	required
outdoor 	air 	rate, 	the 	larger 	quantity 	shall 	be 	used 	for
calculating 	the 	cooling 	load.
(d) 	Control. 	Provision 	for 	reasonable 	control 	of
temperature 	shall 	be made 	for 	all 	air 	conditioning
systems. 	[Eff. 	JAN 3 1 1983 	] 	(Auth: 	HRS 	§§321-9,
3 21-11 ) 	( Imp : 	HRS 	§ § 3 21-1 , 	3 21-11 )
§11-39-8 	Outdoor 	air 	supply. 	(a) 	The 	outdoor
air 	shall 	be 	taken 	from 	a 	clean, 	uncontaminated 	source.
(b) 	Outdoor 	air 	shall 	be 	ducted 	to 	the 	air 	condi-
tioning 	or 	ventilating 	apparatus, 	or mixed with
recirculating 	air 	in 	a 	plenum. 	Wherever 	the 	outdoor
air 	duct 	is 	not 	connected 	to 	the 	apparatus, 	the mixing
plenum 	shall 	be 	properly 	engineered 	and 	free 	from 	air
contamination 	sources.
(c) 	All 	outdoor 	air 	intakes 	shall 	be 	screened 	and
shall 	be 	located 	as .far 	as 	possible 	from 	stacks 	and
vent 	outlets, 	but 	this 	distance 	shall 	in 	no 	case 	be
less 	than 	twelve 	feet 	(three 	and 	five-tenths 	metres).
Domestic 	clothes 	dryer 	vents 	shall 	not 	be 	considered as
outlets 	for 	this 	purpose. 	The 	distance 	in 	each 	case
shall 	be 	sufficient 	to 	prevent 	the 	discharged 	air 	from
entering 	the 	outdoor 	air 	intake.
(1) 	All 	outdoor 	air 	intakes 	shall 	be 	located 	to
be 	readily 	accessible 	for 	cleaning 	and 	shall
39-5
4 	8
§11-39-8
----------~---:-_b_e~kep_t__in_a:_cl.ean-and--S.a¾l-i--l;a-:i:;c-y--eenEl.-i--e-ie.,,,-_________~~}
(2) 	Openings 	for 	outdoor 	air 	intake 	shall 	be 	.J
designed 	so 	that 	the 	air 	face 	velocity 	at 	the
intake 	does 	not 	exceed 	one 	thousand 	feet 	per
minute 	(five 	metres 	per 	second).
(d) 	The 	outdoor 	air 	from 	air 	conditioning 	systems
shall 	be 	supplied 	through 	a 	conditioning 	apparatus
directly 	to 	each 	given 	space 	during 	its 	occupied hours,
and 	the 	quantity 	shall 	conform 	to 	the 	requirements 	of
ASHRAE 	Standard 	62. 	There 	shall 	be 	an 	exception 	to
this 	for 	occupancies 	such 	as 	hotel 	guestrooms, 	apart-
ments, 	or 	dormitories 	where 	air 	conditioning 	is 	provided
within 	separate 	tenancies 	of 	a 	multi-room 	housing 	type
facility, 	and 	where 	openable window 	air 	ratio 	to 	floor
area 	is 	provided 	in 	accordance 	with 	administrative
rules 	and 	building 	codes, 	no 	outdoor 	air 	intake 	shall
be 	required. 	This 	exception 	should 	not 	apply 	to 	nursing
homes, 	hospitals, 	or 	similar medical 	facilities.
(1) 	Outdoor 	air 	quantities 	for 	ventilation 	systems
shall 	be 	provided 	by means 	of 	supply 	or
exhaust 	fans, 	and 	shall 	conform 	to 	the 	require-
ments 	of 	ASHRAE 	Standard 	62.
(2) 	The 	volume 	of 	outdoor 	air 	provided 	for
sparsely-occupied 	areas 	other 	than 	those
specifically 	named 	herein, 	shall 	not 	in 	any
case 	be 	less 	than 	five 	hundredths 	cubic 	feet
per minute 	per 	square 	foot 	(twenty-five
hundredths 	liter 	per 	second 	per 	square metre)
of 	floor 	space.
(3) 	The 	outdoor 	air 	rate 	for 	uses 	or 	occupancies
other 	than 	those 	specifically 	named 	in ASHRAE
Standard 	62 	shall 	be 	by 	agreement 	between 	the
designer 	and 	the 	director.
(4) 	If 	agreed 	between 	the 	designer 	and 	the
director, 	a 	particular occupancy 	in which
tobacco 	smoking 	is 	illegal 	and 	does 	not
occur, 	may 	have 	reduced 	outdoor 	air 	require-
ments, 	where 	based 	on 	a 	specified 	amount 	per
person 	in ASHRAE 	Standard 	62, 	by 	seventy-five
per 	cent, 	provided 	a 	minimum of 	five 	cfm per
person 	(two 	and 	five 	tenths 	liters 	per 	second
per 	person) 	is 	provided.
(5) 	Use 	of 	activated 	carbon or 	other 	odor-
removing means 	shall 	not 	be 	considered 	to
reduce 	the 	required minimum outdoor 	air
quantities. 	[Eff. 	JAN311983 	] 	(Auth:
HRS 	§§321-9, 	321-11) 	(Imp: 	HRS 	§§321-1,
321-11)
§11-39-9 	Air movement, 	distribution, 	recirculation,
and 	removal. 	(a) 	Air movement 	and 	distribution 	and
outdoor 	air 	supply 	shall 	be maintained without 	inter-
ruption 	during 	occupied 	hours 	in 	accordance 	with 	good
39-6
§11-39-10
engineering 	practice. 	Proper 	provision 	for 	balancing
air 	distribution 	shall 	be made 	both 	in 	duct 	design 	and
air 	distribution 	device 	application. 	Air-handling
units 	shall 	operate 	continuously, 	that 	is 	without
interruption, 	while 	the 	space 	is 	occupied 	except 	as
provided 	in ASHRAE 	Standard 	62.
(b} 	Air may 	be 	recirculated 	except where 	not
permitted 	for 	hospitals 	and medical 	facilities 	and
except 	that 	no 	air 	from 	rooms 	with 	obnoxious 	or 	offensive
odors 	or which 	is 	contaminated 	by other 	than 	human
occupancy 	shall 	be 	used 	for 	recirculation 	or 	for 	the
ventilation 	of 	another 	room 	or 	enclosure.
(c) 	Adequate 	provisions 	shall 	be made 	for 	air
removal 	from 	the 	enclosure 	by 	exfiltration 	or 	by 	natural
or mechanical 	exhaust. 	Motivating 	force, 	location 	of
outlets 	and 	the 	volume 	of 	air 	removed 	through 	each
identified 	outlet 	shall 	be 	shown 	on 	the 	plans.
(1) 	Air 	from 	occupied 	areas 	uncontaminated by
other 	than 	human 	occupancy 	and without 	odor
may 	be 	discharged 	into 	corridors 	thence
ventilated 	through 	toilet 	rooms 	or 	other
auxiliary 	rooms.
(2) 	Exhaust 	systems 	serving 	toilet 	rooms 	or 	other
places 	with which 	odors 	or 	similarly 	offensive
conditions 	are 	associated 	shall 	have 	negative
air 	pressure.
(3) 	Kitchen 	exhausts 	shall 	not 	be 	combined 	on 	the
same 	ducts 	or 	fans 	or with 	any 	other 	exhausts.
Clothes 	dryer 	exhausts 	may 	be 	combined with
toilet 	exhausts.
(4) 	In 	a 	building 	higher 	than one 	floor, 	where
toilets 	or 	kitchens 	on more 	than 	one 	floor
are 	served 	by 	the 	same 	exhaust 	fan, 	the 	fan
shall 	be 	continuously 	operated during 	periods
when 	the 	building 	is 	occupied. 	[Eff.
JAN 3 1 	] 	(Auth: 	HRS 	§§321-9, 	321-11}
(Imp: 	HRS 	§§321-1, 	321-11}
§11-39-10 	Hospitals 	and medical 	facilities. 	Air
conditioning 	systems 	used 	in 	hospitals 	and 	other medical
facilities 	including 	long-term 	care 	facilities 	such 	as
nursing 	homes, 	chronic 	disease 	hospitals 	and 	extended
care 	facilities, 	health 	centers 	and medical 	laboratories
shall 	be 	designed 	in 	accordance 	with 	the 	requirements
of 	the 	ASHRAE Handbook 	referenced 	in 	§11-39-3(1) 	and
shall 	conform to 	the 	Minimum Requirements 	of 	Construc-
tion 	& Equipment 	for 	Hospital 	& Medical 	Facilities 	as
published 	by 	the 	U. 	S. 	Department 	of 	Health 	and 	Human
Services 	(Publication No. 	HRA 	79-14,500, 	U. 	S. 	Govern-
ment 	Printing 	Office 	1978). 	[Eff. 	JA 	~ 1 1983 	]
(Auth: 	HRS 	§§321-9, 	321-11) 	(Imp: 	HRS 	§§321-1,
321-11)
39-7
4
§11-39-11
_________->-Ull-3 9-lJ._____Air_fJl±:r:ation_apparatus--(-a)-F-i-~teFs--------~
or 	approved 	air 	cleaning 	devices 	shall 	be 	installed 	in 	_}
connection with 	all 	air 	conditioning 	systems. 	This
requirement 	shall 	apply 	to 	all 	air 	handled 	except
exhaust 	air.
(b) 	Requirements 	of 	air 	purity with 	regard 	to
dust 	contained 	therein 	shall 	be 	assumed 	to 	be 	met 	if
satisfactory 	and 	dependable 	means 	are 	provided 	for
removal 	of 	particulate matter 	as 	follows, 	for 	other
than 	hospital-type 	occupancies:
(1) 	ASHRAE weight 	arrestance 	(where 	applicable 	to
filter 	type) 	shall 	exceed 	fifty 	per 	cent 	and
ASHRAE 	dust 	spot 	efficiency 	shall 	exceed 	ten
per 	cent, 	for 	filters 	of 	all 	air 	conditioning
systems 	and 	mechanical 	ventilation 	supply
systems.
(2) 	For 	air 	conditioning 	apparatus 	other 	than
terminal 	units 	serving 	a 	single 	room or 	a
single 	residential 	apartment ASHRAE weight
arrestance 	shall 	exceed 	seventy-five 	per 	cent
(where 	applicable 	to 	filter 	type), 	and ASHRAE
dust 	spot 	efficiency 	shall 	exceed 	fifteen 	per
cent.
(3) 	For 	hospital-type 	occupancies, 	filter
efficiencies 	shall 	conform 	to 	§11-39-10.
(c) 	Air 	velocity 	in 	conjunction with 	specific
types 	of 	air 	cleaning 	devices 	shall 	not 	exceed 	the
values 	established 	for 	such 	devices 	by 	their manu-
facturer.
(d) 	Air 	filters 	and 	their 	immediate 	accessories
shall 	be 	of 	non-combustible 	or 	fire-resistant 	material.
[Eff. 	JAN 3 1 1983 	] 	(Auth: 	HRS 	§§321-9, 	321-11)
(Imp: 	HRS 	§§321-1, 	321-11)
§11-39-12 	Systems 	for 	ventilating 	only.
(a) 	Ventilating 	systems 	within 	the 	scope 	of 	these
rules 	shall 	provide 	the 	required 	ventilation 	service
for 	all 	occupied 	areas 	for 	which 	such 	form of 	ventila-
tion 	is 	to 	be 	used. 	Systems 	shall 	comply with 	all
applicable 	provisions 	hereinbefore 	listed. 	Ventilation
air 	quantities 	shall 	be 	guided 	by ASHRAE 	Standard 	62.
Filtration 	shall 	be 	applied 	to mechanical 	ventilation
supply or make-up 	air.
(b) 	Ventilation 	for 	restaurant 	cooking 	equipment.
(1) 	Ventilation 	for 	restaurant 	cooking 	equipment
shall 	be 	guided by NFPA Standard 	96.
(2) 	Where 	the 	designer 	prefers 	not 	to 	exhaust
above 	the 	highest 	roof, 	and 	higher 	than 	any
adjacent 	roof 	at 	the 	property 	line, 	a 	grease
vapor 	collector, 	exhaust 	fan, 	and 	fire 	barrier
system approved 	by 	a 	nationally-recognized
testing 	agency, 	may 	be 	used 	instead, 	provided
39-8
§11-39-13
the 	designer 	furnishes 	details 	in 	his 	permit
application, 	the 	installation 	is 	in 	accordance
with 	the 	agency's 	approval.
(3) 	Hood 	and 	duct 	design 	shall 	be 	indicated 	on
plans, 	to 	scale, 	with 	exhaust 	air 	and 	filtered
make-up 	air 	quantities 	indicated.
(4) 	Hood 	design 	shall 	conform 	to 	figure 	1 	dated
July 	1981 	and 	figure 	2 	dated 	July 	1981 	located
at 	the 	end 	of 	this 	chapter; 	or 	design 	computa-
tions 	or 	test 	results 	satisfactory 	to 	the
director 	shall 	be 	provided.
(c) 	Toilet 	exhaust 	shall 	be 	four 	cfm per 	square
foot 	of 	toilet 	room 	floor 	area. 	If 	the make-up 	air 	is
air 	conditioned, 	the 	exhaust 	rate may 	be 	reduced 	to 	two
cfm per 	square 	foot. 	[Eff. 	JAN 3 1 1983 	] 	(Auth:
HRS 	§§321-9, 	321-11) 	(Imp: 	HRS 	§§321-1, 	321-11)'
§11-39-13 	Garage 	ventilation. 	Ventilation 	for
enclosed 	automobile 	parking 	garages 	shall 	be 	guided 	by
the 	following:
(1) 	Each 	story 	or 	level 	of 	a 	parking 	garage 	shall
be mechanically 	ventilated 	unless 	all 	of 	the
following 	requirements 	are 	met:
(A) 	More 	than 	half 	the 	wall 	area 	is 	open, 	in
a 	wall 	length 	of 	at 	least 	(forty 	per
cent) 	the 	perimeter;
(B) 	There 	is 	no 	parking 	attendant 	or 	other
employee 	normally working 	in 	the 	space;
and
(C) 	There 	is 	no 	such unusual 	or 	irregular
shape 	of 	the 	story 	or 	level 	that 	the
majority 	of 	the 	area would 	usually 	not
receive 	natural 	air 	motion.
(2) 	Mechanical 	ventilation 	for 	parking 	garages
shall 	require 	a 	minimum of 	one 	and 	five
tenths 	cfm per 	square 	foot 	(seven 	and 	five
tenths 	liters 	per 	second'per 	square metre)
over 	the 	entire 	floor 	area 	requiring 	ventila-
tion. 	At 	locations 	where 	traffic 	is 	such
that 	congestion 	can 	occur, 	for 	example 	at 	an
exit, 	the 	air 	distribution 	shall 	be 	adjusted
to 	provide more 	air.
(3) 	Ventilation may 	be 	by 	supply 	or 	exhaust, 	but
shall 	be 	arranged 	for 	reasonably 	even 	air
distribution.
(4) 	An 	engineered 	system may 	be 	employed, 	using
the 	equation: 	Q = Kn/C, 	where 	Q = exhaust
ventilation 	rate, 	cfm; 	K = 1,380,000 	(a
constant); 	n 	= number 	of 	cars 	running 	at 	one
instant; 	C = allowable 	carbon monoxide
concentration, 	parts 	per 	million. 	For
residential 	parking 	garages, 	n 	= 1.18 	per
39-9
4
§11-39-13
cent 	of 	total 	parking 	spaces. 	For 	other
------------~p~a-;;;.1rk•1ng 	garages, 	n 	may 	be 	higher. 	For
engineered 	systems 	C shall 	be 	selected with
regard 	to 	threshold 	limit 	CO 	and 	as 	approved
by 	the 	director. 	[Eff. 	JAN 3 1 1983 	]
(Auth: 	HRS 	§§321-9, 	321-11) 	(Imp: 	HRS
§§321-1, 	321-11)
§11-39-14 	Right 	to 	inspect. 	The 	director, 	upon
showing 	credentials, 	shall 	be 	granted 	entrance 	to 	any
building 	premises 	at 	any 	reasonable 	hour 	and 	permitted
to 	inspect 	or 	reinspect 	or 	to 	otherwise 	investigate 	an
air 	conditioning 	or 	ventilating 	system or 	any 	of 	its
component 	parts 	or 	the 	conditions 	resulting 	therefrom
for 	compliance 	with 	the 	provisions 	of 	this 	chapter.
[Eff. 	JAN 3 1 1983 	] 	(Auth: 	HRS 	§§321-9, 	321-11)
(Imp: 	HRS 	§§321-1, 	321-11)
§11-39-15 	Variation. 	If 	the 	director 	finds 	that
there 	are 	great 	practical 	difficulties 	or 	unnecessary
hardships 	in 	complying with 	these 	rules, 	the 	director
may make 	a 	variation 	or 	temporarily 	set 	aside 	such
requirements 	if 	the 	spirit 	of 	the 	provision 	shall 	be
observed 	and 	public 	health, 	safety, 	and 	welfare 	assured.
If 	the 	director 	permits 	such 	variation, 	it 	shall 	apply
to 	all 	buildings, 	installations, 	or 	conditions 	where
the 	facts 	are 	substantially 	the 	same. 	A file 	of 	such
variations 	shall 	be maintained 	in 	the 	department 	and
this 	file 	shall 	be 	periodically 	reviewed 	for 	the 	purpose
of 	improving 	the 	rules 	and 	keeping 	them 	current. 	[Eff.
JAN 3 1 1983 	] 	(Auth: 	HRS 	§§321-9, 	321-11) 	(Imp:
HRS 	§§321-1, 	321-11)
§11-39-16 	Penalty 	for 	violation. 	(a) 	Any 	person
violating 	any 	provision 	of 	this 	chapter 	shall 	be 	subject
to 	the 	penalties 	specified 	in 	section 	321-18, 	HRS.
(b) 	Any 	permittee 	or 	permit 	applicant 	violating
any 	provision 	of 	this 	chapter 	shall 	be 	subject 	to
permit 	revocation, 	suspension, 	or 	denial. 	[Eff.
JAN 3 1 1983 	] 	(Auth: 	HRS 	§§321-9, 	321-11) 	(Imp:
HRS 	§§321-1, 	321-11)
§11-39-17 	Severability. 	If 	any 	provision 	of 	this
chapter, 	or 	the 	application 	thereof 	to 	any 	person 	or
circumstance 	is 	held 	invalid, 	the 	invalidity 	does 	not
affect 	other 	provisions 	or 	applications 	of 	the 	chapter
which 	can 	be 	given 	effect without 	the 	invalid 	provision
or 	application, 	and 	to 	this 	end 	the 	provisions 	of 	this
chapter 	are 	severable. 	[Eff. 	JAN 5 1 j~93 	] 	(Auth:
HRS 	§§321-9, 	321-11) 	(Imp: 	HRS 	§§321-1, 	321-11)
39-10
EOFM l
t.EP~-r OF HEAL'IH
S'!ATE OF ~.JAII
IDISE & P.ADIAT!CN BP,All;Qi
ll.'VIRJ,.~"TF!L ProrECTICN &
Hl:AIJ.IH. SEF.VICES DIVISICN
I
I APPLICATION FOR P.EP}IIT 	ICf Air Conditioning 	CJ Ventilation
(Submit an original and a duplicate with one :set of plans. 	Or.e OOP';{ wil.1. 1::e returned
after review if p,oJ:Ini.t is granted.)
J: hf.!.rcl:rJ apply for a ~t on the project descrfred b:?low and enclose- plans which ~re
prepared b-.f ire or u:.cer ny direct su_.:ervisicn. 	I certify that to fr.e !:est of W>.f kncwledge
the cesign is in O:Jrtplete aco::n:d.ance with the Air Conditioning and Ventilaticn P.egulations
of the ~pa.rtn-ent of Health. 	(Excspt. as noted 'llnd.:r "~-")
FIR-i & Th'GINEER 	PFOJECl'
Finn: 	Nan-e:
.Engineer s Na.-ra: 	J!i!dress:
..iddress: 	City:
City: 	Zip:
Zip: 	Phone:
'fype of 	Iesign 	OUt: 	rn 	'WB
Occupancy 	Cbrrlitions 	rn: 	D3 	% F".d
Project
tnit or ZCne No.* 	'Ibtal
11.rea Served (N2!re)
Cond1.tioned A..i-ea, :,q. Ft.
Persons Cccuovinq
Outco::,r: Air, CFH
2.1£PlY Air, CTM
Z,:,ne 'Ibta.J. Heat, B'IUi
lliusual Heat, BTUI
E'CTUJ.::m?.nt Ca=ci t:{, 'IbnS
Exhaust: 	GH
: 	Iocat.l.Cn
P...:!I!'0l:k.s: .
i:ZPARI'!-!ENT OF HE.il.L'IH SECTICN 	ENGINEER'S CERI'IFICAT!CN
?ernu.t: for ir.st:all.ati.on, aJ.te..-aticn or operation 	Signatti:re;
is granted in aa::or~ wi-th this awlicatlon
clild its ao:::a:-""~ plans~ 	'Ihis p=-...rmit is
Irevocable for cause. 	Wit:hin 60 days after
c::irrpletion of the system, the applicant shall
mt.L.~ the Iepa...-t::rent: oE Health in w.citing 	Date:
that the 5i-stem is installed. and ~ting
l si.1bstantially as desigied.
Signa.ture:
Narre: 	El'lgineo...r. s
Title: 	seal
shalJ.
re
P£R."1IT ~lO. I 	03te: 	affb:ed
?ecr.arks:
I •.Attach acditimal pases if :rrore cata required.
4 7 8
Duels s•OQ c<!t7ler me;,
lvr /arae, lroods 	I .
cr:.::1:::.r_-:r=£::1:.::r=.1:::1l--~--L_J_ __ l ___L__ i __ J_ __ t __ J
--------L -----------i
J____c_oo_l:._:in_g_~_q:i_ipm_em_t ____--11
H=4°m(;;(imum 	7t 6 .. mli;in'rJm
0;1er'111ng
HOOD AGAINST WALL
O= BO cfm/sq fl of hood area ( 80 £'/l}
Nol less than- 50 cfm/sq fl of face area (SOFH} 	P=~ri~fe.r of f,o,-A.
Cucf velocity= /000-4000 fpm, to sol/ conditions 	. 	= 2W+'i_
Entry loss ={filler reslslarr-e -JQJ') .J-0.50 VP(straighl take off}
Entry loss =(filler resi'slance +O.l'J+ Q25VP(lapared fa,fo off}
,-,---,--r--:--:--~---r--r--1
t-~--..:.---:---},--..1---:.---.;-----;	I 	I 	1 	I 	•t 	: 	I 	I 	: 	I	
l __ .1 __ ... __ J ___L _ __. ___•___ .1.. __ ._ __J
L--------,-,.j-L c" mrmmu~W 	,,,;_
l
i:======~1 	":u:t::""· 	D·:. 	Islam/ coo!ang area 	=
ISLAND TYPE HOOD
O =125 elm/sq fl of J-,ood area (/25 WL) 	.
Not less than 50 elm/sq fl of faca area (50 PH} 	f=per,mde,, of hood
l}ucl velocity= /000-4000 fpm. lo suit cc:iditioas 	=2W+2l.
Entry loss =(filter reslsfancelO./'J+ O.SOVP (s!n:tlg/Jf lake off)
Entry loss:::(filter reslslance f QJjf 0.25 VP(laper6d take oft}
Note:
See VS-911 for lnformatlon
ubcut filters and fans
KITCHEN RANGE HOODS
Figure 1
7 8
Filters:
oce ol' ends car, Iii:!'
oper.e:J lei' lillel'
remo110I
,-ma:rlimin,
.set-bacir
Fifi:!,, mounhnghelgl:I 	.;1•n;ax/mum
See nole 4 be/ow.
l
------L-----"M 	Closed ends thslra!Ji
Cooking eqaip,r.t:f:I
LOW SIDE WALL HOOD
0=200 cfm//ii;~/ ft of co&ing surface (200 lJ
Doc/ ve/ocity=J000-4000fpm1 la s-Jit conditions 	.
Eofry /oss:;(filter resistcmce+O.J''}.;. Q5VP(slraig/Jf tale off'}
Entry loss= (filler resistar.ce -f o.!''} ,j, 0.25 VP{tapered /axe off)
NOTES FOR KITCHEN HOODS
Fillers:
l 	Se/act pracllcal /J7ter size.
2. De/ermine number of fillers raquired from mcrnufaclurers data.
(Usuol!y: 2 cfln moxlmum exhaust for each sq in af filler aret7}
3. lnsta/1 at 45°- 60° Jo /Jcrizonlal. 	/tle-,1er /Jorizonla/.
4. Filler mounting helght (Reference 66) 	• 	• • 	• 	•
· a. No exposed cooking /Jome- If• mJiinl!1m lo fewest ed'r;e, er n7ter.
b. Ctrr:rcool and similar tires-- 4'minimum to low0sl edge of filler.
5. Shield fillers from dlrecf radiant /Jeof.
6. Pro:tide removable grease drip pan.
7. Clean pan and filters regularly.
Fan: 	. 	.
l. Use upblasl discharg[! fan. Oo;;,nblasl is· not r-:ccmmended
2. Select /'on for design O and
SP resls!cnce of fillers ar.d
duclr1or:r.
3.. Ac!jusl fan specification
for expected ex/Jaus/ air
tempera/we.
KITCHEN RANGE HOOD
Figure 2
7 8