§11-39-1 §11-39-2 §11-39-3 §11-39-4 §11-39-5 §11-39-6 §11-39-7 §11-39-8 §11-39-9 §11-39-10 §11-39-11 §11-39-12 §11-39-13 §11-39-14 §11-39-15 §11-39-16 §11-39-17 TITLE 11 DEPARTMENT OF HEALTH CHAPTER 39 AIR CONDITIONING AND VENTILATING Purpose Definitions References General requirement Exemptions Permit Design conditions Outdoor air supply §11-39-2 Air movement, distribution, recirculation, and removal Hospitals and medical facilities Air filtration apparatus Systems for ventilating only Garage ventilation Right to inspect Variation Penalty for violation Severability Historical Note: Chapter 39 of Title 11, Adminis- trative Rules, is based substantially on Public Health Regulations Chapter 28, Air Conditioning and Ventilating, Department of Health, State of Hawaii. [Eff. 7/1/53, am 5 / 6 / 6 4 , am 8 / 17/64 ; R J A N 3 1 19 83 §11-39-1 Purpose. These rules are adopted under chapter 91, HRS and implements section 321-11(13), HRS and the following objectives: (1) Seek to assure the adequate and healthful design, construction, installation, and operation of comfort air conditioning and ventilating systems. (2) Provide minimum ventilation requirements. [Eff. JAN 3 1 1983 ] (Auth: HRS §§321-9, 321-11) (Imp: HRS §§321-1, 321-11) §11-39-2 Definitions. As used in this chapter: "Designer" means a registered architect or a professional engineer especially qualified in the mechanical branch. "Department" means the department of health of the 39-1
§11-39-2 --------&eaee-e~-&awa±~·-.--------------------------------;--'~ "Director" means the director of the department of health or a duly authorized agent or representative. "Mechanical branch" means one of seven specialties in the field of engineering in which a professional license is issued under chapter 464, HRS, and chapter 147, Title 12, Administrative Rules of the Board of Professional Engineers, Architects, Surveyors, and Landscape Architects. Refer to chapter 147, Title 12 for list of specialties. "Permit" means a permit issued to a designer under this chapter. "Public buildings" mean any structure used in whole or in part as a place or resort, assemblage, lodging, business, industry, trade, traffic, occupancy or use by the public or by a segment of the public, or by three or more tenants. "Seal" means an identification stamp as an evidence of registration as a professional architect or pro- fessional engineer especially qualified in the mechanical branch by the State of Hawaii. All technical definitions for this rule shall be governed by the American Society of Heating, Refrigera- ting, and Air-Conditioning Engineers' Handbooks: Fundamentals, Equipment, Systems, and Applications. [Eff. JAN 3 1 1983 ] (Auth: HRS §§321-9, 321-11) (Imp: HRS §§321-1, 321-11) §11-39-3 References. The following references shall be used as a guide for good engineering practice: (1) Handbooks of the ASHRAE (American Society of Heating, Refrigerating and Air-conditioning Engineers): Fundamentals (1981 edition), Equipment (1979 edition), Systems (1980 edition), and Applications (1982 edition). (2) Safety Code for Mechanical Refrigeration, American National Standards Institute (ANSI) Standard ANSI/ASHRAE 15, 1978 edition. (3) Industrial Ventilation - Manual of Recommended Practice American Conference of Government Industrial Hygienists, 1980 edition. (4) Standard for Ventilation for Acceptable Indoor Air Quality. ASHRAE Standard 62, 1981 edition. (5) Thermal Environmental Conditions for Human Comfort. ASHRAE Standard 55, 1981 edition. (6) NFPA (National Fire Protection Association) Standard 90A. Standard for the Installation of Air Conditioning and Ventilating Systems, 1978 edition. (7) NFPA Standard 96. Removal of Smoke and Grease-Laden Vapors from Commercial Cooking 39-2
§11-39-4 Equipment, 1980 edition. (8) SMACNA (Sheet Metal & Air Conditioning Con- tractors' National Association) low pressure duct construction standards, 1976 edition. [Eff. JAN311983 ] (Auth: HRS§§321-9, 3 21-11 ) ( Imp : HRS § § 3 21-1 , 3 21-11 ) §11-39-4 General requirements. The provisions of these rules apply when a comfort air conditioning system or a ventilating system is to be installed in buildings used or to be used as public buildings. (1) New buildings. These rules apply to all new buildings. New buildings mean buildings, additions thereto and alterations thereof, for which plans have not been approved by the department previously or construction was not in progress prior to the effective date of these rules. (2) Existing buildings. These rules apply to all alterations or improvements to existing buildings, including the replacement of any major apparatus or device related to air conditioning or ventilating systems. Existing buildings mean buildings, additions thereto and alterations thereof, structurally com- pleted or for which plans have been approved by the department and construction is in progress prior to the effective date of these rules. (3) Change in use. These rules apply to every building, or portion of a building, devoted to new use for which the requirements under these rules are more stringent than the requirements covering the previous use. (4) Design and preparation of plans. All plans and data on air conditioning and ventilating systems shall be prepared by or under the direct supervision of a "designer." All air conditioning insta1lations shall be designed and installed to provide proper comfort as defined in ASHRAE Standard 55, unless con- strained by laws of the United States of America or the State of Hawaii for reasons of conservation of energy. (5) Refrigeration system. The entire installation of refrigeration in connection with air conditioning shall be in accordance with good engineering practice and the provisions of ANSI/ASHRAE 15. (6) User's responsibility. All users shall maintain air conditioning and ventilating systems in good working order and shall 39-3 7 8
§11-39-4 _____________ope:r:a-t.e~t.hem--se-a-s--to-prov±d~e-a-ccepEab7:e atmospheric conditions in the enclosure during all periods of occupancy. (7) Provisions for cleanliness. All parts of installations and equipment which house or handle air used for ventilating purposes shall be designed so as to facilitate sanitary maintenance thereof. [Eff. JAN 3 1 1983 ] (Auth: HRS §§321-9, 321-11) (Imp: HRS §§321-1, 321-11) §11-39-5 Exemptions. These rules do not apply to the types of systems named below. (1) Units of four and one-fourth tons refrigeration (fifteen kilowatt) cooling capacity or less are exempt from §11-39-6 provided that they are not part of a multiple installation, with a combined capacity greater than four and one-fourth tons (fifteen kilowatt) furnished to ventilate any room or similar single enclosure; all other sections of this rule shall remain applicable to units of four and one-fourth tons (fifteen kilowatt) or less. (2) Ventilating systems including multiple installation with a total of two thousand one hundred cubic feet per minute (one thousand litres per sec) capacity or less are governed by these rules but no permit is required. [Eff. JAN311983 ] (Auth: HRS §§321-9, 3 21-11 ) ( Imp : HRS § § 3 21-1 , 3 21-11 ) §11-39-6 Permit. (a) No person shall install, alter, or operate an air conditioning or ventilating system without first obtaining from the department a valid permit covering the specific installation, altera- tion, or operation. (b) Form 1, Application for Permit, dated July 1981, located at the end of this chapter shall be used as a permit application form and permit. (c) Revocation, suspension, or denial of permit. The department may on its own motion, or on the complaint of any person, revoke, suspend, or deny a permit after notifying the permittee or applicant and offering him an opportunity to be heard. Revocation, suspension, or denial of a permit shall be grounded on a violation of this chapter. [Eff. JAN 3 1 1983 ] (Auth: HRS §§321-9, 321-11) (Imp: HRS §~321-1, 321-11) §11-39-7 Design conditions. (a) Outside and inside design conditions. The following design condi- 39-4
§11-39-8 tions shall be used for air conditioning systems which will be operated at near maximum load in daylight hours, at elevations below three thousand two hundred eighty-one feet (one thousand metres) above sea level: OUTSIDE INSIDE Dry Bulb 87°F (30.6°C) or higher Wet Bulb 75°F (23.9°C) or higher Dry Bulb 78°F (25.6°C) or lower Relative Humidity 60% or lower By special application to the director the above condi- tions may be modified for systems whose loads peak at times when outdoor temperature is much lower than daily maximum or systems at higher altitudes, and in this case design condition shall be as agreed between the designer and the director. (b) Design cooling load. Minimum allowances to be made in estimating the net instantaneous heat gains in a building shall be in accordance with good engineering practice. (c) Infiltration. Infiltration air volume rate and the sensible and latent heat gains therefrom shall be determined for air conditioning systems; and where calculated infiltration rate differs from required outdoor air rate, the larger quantity shall be used for calculating the cooling load. (d) Control. Provision for reasonable control of temperature shall be made for all air conditioning systems. [Eff. JAN 3 1 1983 ] (Auth: HRS §§321-9, 3 21-11 ) ( Imp : HRS § § 3 21-1 , 3 21-11 ) §11-39-8 Outdoor air supply. (a) The outdoor air shall be taken from a clean, uncontaminated source. (b) Outdoor air shall be ducted to the air condi- tioning or ventilating apparatus, or mixed with recirculating air in a plenum. Wherever the outdoor air duct is not connected to the apparatus, the mixing plenum shall be properly engineered and free from air contamination sources. (c) All outdoor air intakes shall be screened and shall be located as .far as possible from stacks and vent outlets, but this distance shall in no case be less than twelve feet (three and five-tenths metres). Domestic clothes dryer vents shall not be considered as outlets for this purpose. The distance in each case shall be sufficient to prevent the discharged air from entering the outdoor air intake. (1) All outdoor air intakes shall be located to be readily accessible for cleaning and shall 39-5 4 8
§11-39-8 ----------~---:-_b_e~kep_t__in_a:_cl.ean-and--S.a¾l-i--l;a-:i:;c-y--eenEl.-i--e-ie.,,,-_________~~} (2) Openings for outdoor air intake shall be .J designed so that the air face velocity at the intake does not exceed one thousand feet per minute (five metres per second). (d) The outdoor air from air conditioning systems shall be supplied through a conditioning apparatus directly to each given space during its occupied hours, and the quantity shall conform to the requirements of ASHRAE Standard 62. There shall be an exception to this for occupancies such as hotel guestrooms, apart- ments, or dormitories where air conditioning is provided within separate tenancies of a multi-room housing type facility, and where openable window air ratio to floor area is provided in accordance with administrative rules and building codes, no outdoor air intake shall be required. This exception should not apply to nursing homes, hospitals, or similar medical facilities. (1) Outdoor air quantities for ventilation systems shall be provided by means of supply or exhaust fans, and shall conform to the require- ments of ASHRAE Standard 62. (2) The volume of outdoor air provided for sparsely-occupied areas other than those specifically named herein, shall not in any case be less than five hundredths cubic feet per minute per square foot (twenty-five hundredths liter per second per square metre) of floor space. (3) The outdoor air rate for uses or occupancies other than those specifically named in ASHRAE Standard 62 shall be by agreement between the designer and the director. (4) If agreed between the designer and the director, a particular occupancy in which tobacco smoking is illegal and does not occur, may have reduced outdoor air require- ments, where based on a specified amount per person in ASHRAE Standard 62, by seventy-five per cent, provided a minimum of five cfm per person (two and five tenths liters per second per person) is provided. (5) Use of activated carbon or other odor- removing means shall not be considered to reduce the required minimum outdoor air quantities. [Eff. JAN311983 ] (Auth: HRS §§321-9, 321-11) (Imp: HRS §§321-1, 321-11) §11-39-9 Air movement, distribution, recirculation, and removal. (a) Air movement and distribution and outdoor air supply shall be maintained without inter- ruption during occupied hours in accordance with good 39-6
§11-39-10 engineering practice. Proper provision for balancing air distribution shall be made both in duct design and air distribution device application. Air-handling units shall operate continuously, that is without interruption, while the space is occupied except as provided in ASHRAE Standard 62. (b} Air may be recirculated except where not permitted for hospitals and medical facilities and except that no air from rooms with obnoxious or offensive odors or which is contaminated by other than human occupancy shall be used for recirculation or for the ventilation of another room or enclosure. (c) Adequate provisions shall be made for air removal from the enclosure by exfiltration or by natural or mechanical exhaust. Motivating force, location of outlets and the volume of air removed through each identified outlet shall be shown on the plans. (1) Air from occupied areas uncontaminated by other than human occupancy and without odor may be discharged into corridors thence ventilated through toilet rooms or other auxiliary rooms. (2) Exhaust systems serving toilet rooms or other places with which odors or similarly offensive conditions are associated shall have negative air pressure. (3) Kitchen exhausts shall not be combined on the same ducts or fans or with any other exhausts. Clothes dryer exhausts may be combined with toilet exhausts. (4) In a building higher than one floor, where toilets or kitchens on more than one floor are served by the same exhaust fan, the fan shall be continuously operated during periods when the building is occupied. [Eff. JAN 3 1 ] (Auth: HRS §§321-9, 321-11} (Imp: HRS §§321-1, 321-11} §11-39-10 Hospitals and medical facilities. Air conditioning systems used in hospitals and other medical facilities including long-term care facilities such as nursing homes, chronic disease hospitals and extended care facilities, health centers and medical laboratories shall be designed in accordance with the requirements of the ASHRAE Handbook referenced in §11-39-3(1) and shall conform to the Minimum Requirements of Construc- tion & Equipment for Hospital & Medical Facilities as published by the U. S. Department of Health and Human Services (Publication No. HRA 79-14,500, U. S. Govern- ment Printing Office 1978). [Eff. JA ~ 1 1983 ] (Auth: HRS §§321-9, 321-11) (Imp: HRS §§321-1, 321-11) 39-7 4
§11-39-11 _________->-Ull-3 9-lJ._____Air_fJl±:r:ation_apparatus--(-a)-F-i-~teFs--------~ or approved air cleaning devices shall be installed in _} connection with all air conditioning systems. This requirement shall apply to all air handled except exhaust air. (b) Requirements of air purity with regard to dust contained therein shall be assumed to be met if satisfactory and dependable means are provided for removal of particulate matter as follows, for other than hospital-type occupancies: (1) ASHRAE weight arrestance (where applicable to filter type) shall exceed fifty per cent and ASHRAE dust spot efficiency shall exceed ten per cent, for filters of all air conditioning systems and mechanical ventilation supply systems. (2) For air conditioning apparatus other than terminal units serving a single room or a single residential apartment ASHRAE weight arrestance shall exceed seventy-five per cent (where applicable to filter type), and ASHRAE dust spot efficiency shall exceed fifteen per cent. (3) For hospital-type occupancies, filter efficiencies shall conform to §11-39-10. (c) Air velocity in conjunction with specific types of air cleaning devices shall not exceed the values established for such devices by their manu- facturer. (d) Air filters and their immediate accessories shall be of non-combustible or fire-resistant material. [Eff. JAN 3 1 1983 ] (Auth: HRS §§321-9, 321-11) (Imp: HRS §§321-1, 321-11) §11-39-12 Systems for ventilating only. (a) Ventilating systems within the scope of these rules shall provide the required ventilation service for all occupied areas for which such form of ventila- tion is to be used. Systems shall comply with all applicable provisions hereinbefore listed. Ventilation air quantities shall be guided by ASHRAE Standard 62. Filtration shall be applied to mechanical ventilation supply or make-up air. (b) Ventilation for restaurant cooking equipment. (1) Ventilation for restaurant cooking equipment shall be guided by NFPA Standard 96. (2) Where the designer prefers not to exhaust above the highest roof, and higher than any adjacent roof at the property line, a grease vapor collector, exhaust fan, and fire barrier system approved by a nationally-recognized testing agency, may be used instead, provided 39-8
§11-39-13 the designer furnishes details in his permit application, the installation is in accordance with the agency's approval. (3) Hood and duct design shall be indicated on plans, to scale, with exhaust air and filtered make-up air quantities indicated. (4) Hood design shall conform to figure 1 dated July 1981 and figure 2 dated July 1981 located at the end of this chapter; or design computa- tions or test results satisfactory to the director shall be provided. (c) Toilet exhaust shall be four cfm per square foot of toilet room floor area. If the make-up air is air conditioned, the exhaust rate may be reduced to two cfm per square foot. [Eff. JAN 3 1 1983 ] (Auth: HRS §§321-9, 321-11) (Imp: HRS §§321-1, 321-11)' §11-39-13 Garage ventilation. Ventilation for enclosed automobile parking garages shall be guided by the following: (1) Each story or level of a parking garage shall be mechanically ventilated unless all of the following requirements are met: (A) More than half the wall area is open, in a wall length of at least (forty per cent) the perimeter; (B) There is no parking attendant or other employee normally working in the space; and (C) There is no such unusual or irregular shape of the story or level that the majority of the area would usually not receive natural air motion. (2) Mechanical ventilation for parking garages shall require a minimum of one and five tenths cfm per square foot (seven and five tenths liters per second'per square metre) over the entire floor area requiring ventila- tion. At locations where traffic is such that congestion can occur, for example at an exit, the air distribution shall be adjusted to provide more air. (3) Ventilation may be by supply or exhaust, but shall be arranged for reasonably even air distribution. (4) An engineered system may be employed, using the equation: Q = Kn/C, where Q = exhaust ventilation rate, cfm; K = 1,380,000 (a constant); n = number of cars running at one instant; C = allowable carbon monoxide concentration, parts per million. For residential parking garages, n = 1.18 per 39-9 4
§11-39-13 cent of total parking spaces. For other ------------~p~a-;;;.1rk•1ng garages, n may be higher. For engineered systems C shall be selected with regard to threshold limit CO and as approved by the director. [Eff. JAN 3 1 1983 ] (Auth: HRS §§321-9, 321-11) (Imp: HRS §§321-1, 321-11) §11-39-14 Right to inspect. The director, upon showing credentials, shall be granted entrance to any building premises at any reasonable hour and permitted to inspect or reinspect or to otherwise investigate an air conditioning or ventilating system or any of its component parts or the conditions resulting therefrom for compliance with the provisions of this chapter. [Eff. JAN 3 1 1983 ] (Auth: HRS §§321-9, 321-11) (Imp: HRS §§321-1, 321-11) §11-39-15 Variation. If the director finds that there are great practical difficulties or unnecessary hardships in complying with these rules, the director may make a variation or temporarily set aside such requirements if the spirit of the provision shall be observed and public health, safety, and welfare assured. If the director permits such variation, it shall apply to all buildings, installations, or conditions where the facts are substantially the same. A file of such variations shall be maintained in the department and this file shall be periodically reviewed for the purpose of improving the rules and keeping them current. [Eff. JAN 3 1 1983 ] (Auth: HRS §§321-9, 321-11) (Imp: HRS §§321-1, 321-11) §11-39-16 Penalty for violation. (a) Any person violating any provision of this chapter shall be subject to the penalties specified in section 321-18, HRS. (b) Any permittee or permit applicant violating any provision of this chapter shall be subject to permit revocation, suspension, or denial. [Eff. JAN 3 1 1983 ] (Auth: HRS §§321-9, 321-11) (Imp: HRS §§321-1, 321-11) §11-39-17 Severability. If any provision of this chapter, or the application thereof to any person or circumstance is held invalid, the invalidity does not affect other provisions or applications of the chapter which can be given effect without the invalid provision or application, and to this end the provisions of this chapter are severable. [Eff. JAN 5 1 j~93 ] (Auth: HRS §§321-9, 321-11) (Imp: HRS §§321-1, 321-11) 39-10
EOFM l
t.EP~-r OF HEAL'IH
S'!ATE OF ~.JAII
IDISE & P.ADIAT!CN BP,All;Qi
ll.'VIRJ,.~"TF!L ProrECTICN &
Hl:AIJ.IH. SEF.VICES DIVISICN
I
I APPLICATION FOR P.EP}IIT ICf Air Conditioning CJ Ventilation
(Submit an original and a duplicate with one :set of plans. Or.e OOP';{ wil.1. 1::e returned
after review if p,oJ:Ini.t is granted.)
J: hf.!.rcl:rJ apply for a ~t on the project descrfred b:?low and enclose- plans which ~re
prepared b-.f ire or u:.cer ny direct su_.:ervisicn. I certify that to fr.e !:est of W>.f kncwledge
the cesign is in O:Jrtplete aco::n:d.ance with the Air Conditioning and Ventilaticn P.egulations
of the ~pa.rtn-ent of Health. (Excspt. as noted 'llnd.:r "~-")
FIR-i & Th'GINEER PFOJECl'
Finn: Nan-e:
.Engineer s Na.-ra: J!i!dress:
..iddress: City:
City: Zip:
Zip: Phone:
'fype of Iesign OUt: rn 'WB
Occupancy Cbrrlitions rn: D3 % F".d
Project
tnit or ZCne No.* 'Ibtal
11.rea Served (N2!re)
Cond1.tioned A..i-ea, :,q. Ft.
Persons Cccuovinq
Outco::,r: Air, CFH
2.1£PlY Air, CTM
Z,:,ne 'Ibta.J. Heat, B'IUi
lliusual Heat, BTUI
E'CTUJ.::m?.nt Ca=ci t:{, 'IbnS
Exhaust: GH
: Iocat.l.Cn
P...:!I!'0l:k.s: .
i:ZPARI'!-!ENT OF HE.il.L'IH SECTICN ENGINEER'S CERI'IFICAT!CN
?ernu.t: for ir.st:all.ati.on, aJ.te..-aticn or operation Signatti:re;
is granted in aa::or~ wi-th this awlicatlon
clild its ao:::a:-""~ plans~ 'Ihis p=-...rmit is
Irevocable for cause. Wit:hin 60 days after
c::irrpletion of the system, the applicant shall
mt.L.~ the Iepa...-t::rent: oE Health in w.citing Date:
that the 5i-stem is installed. and ~ting
l si.1bstantially as desigied.
Signa.ture:
Narre: El'lgineo...r. s
Title: seal
shalJ.
re
P£R."1IT ~lO. I 03te: affb:ed
?ecr.arks:
I •.Attach acditimal pases if :rrore cata required.
4 7 8Duels s•OQ c<!t7ler me;,
lvr /arae, lroods I .
cr:.::1:::.r_-:r=£::1:.::r=.1:::1l--~--L_J_ __ l ___L__ i __ J_ __ t __ J
--------L -----------i
J____c_oo_l:._:in_g_~_q:i_ipm_em_t ____--11
H=4°m(;;(imum 7t 6 .. mli;in'rJm
0;1er'111ng
HOOD AGAINST WALL
O= BO cfm/sq fl of hood area ( 80 £'/l}
Nol less than- 50 cfm/sq fl of face area (SOFH} P=~ri~fe.r of f,o,-A.
Cucf velocity= /000-4000 fpm, to sol/ conditions . = 2W+'i_
Entry loss ={filler reslslarr-e -JQJ') .J-0.50 VP(straighl take off}
Entry loss =(filler resi'slance +O.l'J+ Q25VP(lapared fa,fo off}
,-,---,--r--:--:--~---r--r--1
t-~--..:.---:---},--..1---:.---.;-----; I I 1 I •t : I I : I
l __ .1 __ ... __ J ___L _ __. ___•___ .1.. __ ._ __J
L--------,-,.j-L c" mrmmu~W ,,,;_
l
i:======~1 ":u:t::""· D·:. Islam/ coo!ang area =
ISLAND TYPE HOOD
O =125 elm/sq fl of J-,ood area (/25 WL) .
Not less than 50 elm/sq fl of faca area (50 PH} f=per,mde,, of hood
l}ucl velocity= /000-4000 fpm. lo suit cc:iditioas =2W+2l.
Entry loss =(filter reslsfancelO./'J+ O.SOVP (s!n:tlg/Jf lake off)
Entry loss:::(filter reslslance f QJjf 0.25 VP(laper6d take oft}
Note:
See VS-911 for lnformatlon
ubcut filters and fans
KITCHEN RANGE HOODS
Figure 1
7 8Filters:
oce ol' ends car, Iii:!'
oper.e:J lei' lillel'
remo110I
,-ma:rlimin,
.set-bacir
Fifi:!,, mounhnghelgl:I .;1•n;ax/mum
See nole 4 be/ow.
l
------L-----"M Closed ends thslra!Ji
Cooking eqaip,r.t:f:I
LOW SIDE WALL HOOD
0=200 cfm//ii;~/ ft of co&ing surface (200 lJ
Doc/ ve/ocity=J000-4000fpm1 la s-Jit conditions .
Eofry /oss:;(filter resistcmce+O.J''}.;. Q5VP(slraig/Jf tale off'}
Entry loss= (filler resistar.ce -f o.!''} ,j, 0.25 VP{tapered /axe off)
NOTES FOR KITCHEN HOODS
Fillers:
l Se/act pracllcal /J7ter size.
2. De/ermine number of fillers raquired from mcrnufaclurers data.
(Usuol!y: 2 cfln moxlmum exhaust for each sq in af filler aret7}
3. lnsta/1 at 45°- 60° Jo /Jcrizonlal. /tle-,1er /Jorizonla/.
4. Filler mounting helght (Reference 66) • • • • •
· a. No exposed cooking /Jome- If• mJiinl!1m lo fewest ed'r;e, er n7ter.
b. Ctrr:rcool and similar tires-- 4'minimum to low0sl edge of filler.
5. Shield fillers from dlrecf radiant /Jeof.
6. Pro:tide removable grease drip pan.
7. Clean pan and filters regularly.
Fan: . .
l. Use upblasl discharg[! fan. Oo;;,nblasl is· not r-:ccmmended
2. Select /'on for design O and
SP resls!cnce of fillers ar.d
duclr1or:r.
3.. Ac!jusl fan specification
for expected ex/Jaus/ air
tempera/we.
KITCHEN RANGE HOOD
Figure 2