780 CMR 27.00 — Chapter 27: Electrical amendments

cmr-780-27.00780 CMR 27.00Regulation

27.00 Chapter 27: Electrical amendments

THIS IS AN UNOFFICIAL COPY OF THE REGULATIONS – OFFICIAL COPIES MUST BE OBTAINED FROM THE SECRETARY OF THE COMMONWEALTH

780 CMR: MASSACHUSETTS AMENDMENTS TO THE INTERNATIONAL BUILDING CODE 2021

CHAPTER 27: ELECTRICAL

2701.1 Revise section as follows:

2701.1 Scope. 780 CMR 27.00 governs the electrical components, equipment and systems used in buildings and structures covered by 780 CMR. Electrical components, equipment and systems shall be designed and constructed in accordance with the provisions of 527 CMR 12.00.

2701.1.1 Revise subsection as follows:

[F] 2702.1.1 Stationary generators. Stationary emergency and standby power generators required by 780 CMR shall be listed in accordance with UL 2200. For air quality control for point source generation see 310 CMR 7:00 Air Pollution Control.

2702.2.2 Revise subsection as follows:

[F] 2702.2.2 Elevators and platform lifts. Standby power shall be provided for elevators and platform lifts as required by 780 CMR and 524 CMR.