Martinez v. Cast, LLC

CourtListener 10360772Coloctapp20.03.2025

Gesamter Gesetzestext

The summaries of the Colorado Court of Appeals published opinions
constitute no part of the opinion of the division but have been prepared by
the division for the convenience of the reader. The summaries may not be
cited or relied upon as they are not the official language of the division.
Any discrepancy between the language in the summary and in the opinion
should be resolved in favor of the language in the opinion.

SUMMARY
March 20, 2025

2025COA32

No. 23CA1909, Martinez v. Cast, LLC — Landlords and Tenants
— Colorado Premises Liability Act — Actions Against Landlords
— International Fire Code

A division of the court of appeals considers which version of a

local fire safety ordinance applies in this premises liability case

arising from a fire at a leased dwelling. The division concludes that,

under the facts of this case, the applicable ordinance was the one in

effect at the time the plaintiff children were injured, not the one in

effect at the time the dwelling was built or the lease was executed.

The division also concludes that, under section 1103.8.1 of the

2012 edition of the International Fire Code — the edition

incorporated into the applicable ordinance — landowners are not

required to comply with the smoke alarm requirements specified in

the 2012 International Fire Code so long as (1) a building code was

in effect at the time of construction; (2) such code required smoke
alarms; and (3) smoke alarms complying with those requirements

were already provided in the dwelling.

The division concludes that the trial court erred by instructing

the jury on an earlier version of the ordinance than the one in effect

at the time the children were injured. Accordingly, it reverses the

judgment entered in favor of the children and remands the case to

the trial court. In addition, the division addresses one of the

defendants’ other arguments, which is likely to recur in the event of

a retrial, and it declines the children’s request for an award of

attorney fees.
COLORADO COURT OF APPEALS 2025COA32

Court of Appeals No. 23CA1909
La Plata County District Court No. 18CV30085
Honorable Kim S. Shropshire, Judge

Anthony Martinez, as father and next friend of Rivers Picasso Martinez, a
minor, and Ira Picasso Martinez, a minor,

Plaintiffs-Appellees,

v.

Cast, LLC, a Colorado limited liability company; Caroni Adams, Inc., a
Colorado corporation, d/b/a The Property Manager; and Carolyn Caroni
Adams,

Defendants-Appellants.

JUDGMENT REVERSED AND CASE
REMANDED WITH DIRECTIONS

Division VII
Opinion by JUDGE LIPINSKY
Johnson and Moultrie, JJ., concur

Announced March 20, 2025

Scott R. Larson, P.C., Scott R. Larson, Broomfield, Colorado; Recht Kornfeld,
P.C., Heather R. Hanneman, Denver, Colorado, for Plaintiffs-Appellees

Sparks Willson, P.C., Jessica L. Kyle, Colorado Springs, Colorado, for
Defendant-Appellant Cast, LLC

Lewis Roca Rothgerber Christie LLP, Kendra N. Beckwith, Denver, Colorado, for
Defendant-Appellant Caroni Adams, Inc.

Campbell, Wagner & Frazier, LLC, Colin C. Campbell, Greenwood Village,
Colorado, for Defendant-Appellant Carolyn Caroni Adams
¶1 The Colorado Premises Liability Act (the Act), § 13-21-115,

C.R.S. 2024, provides the sole remedy against landowners for

injuries on their property. Wycoff v. Grace Cmty. Church of

Assemblies of God, 251 P.3d 1260, 1265 (Colo. App. 2010). The Act

divides those persons to whom a landowner owes a duty of care into

three categories — trespassers, invitees, and licensees.

§ 13-21-115(4).

¶2 Landowners owe different duties to each category of persons.

A person “who enters or remains on the land of another” for the

person’s “own convenience or to advance the [person’s] own

interests, pursuant to the landowner’s permission or consent,” is a

“licensee” under the Act. § 13-21-115(7)(c). “[S]ocial guest[s]” are

licensees. Id.

¶3 As relevant to this case, “[a] licensee may only recover

damages caused . . . [b]y the landowner’s unreasonable failure to

exercise reasonable care with respect to dangers created by the

landowner that the landowner actually knew about.”

§ 13-21-115(4)(b)(I). A landowner may be held liable to a licensee

who was injured on the landowner’s property as a consequence of

the landowner’s failure to comply with a local ordinance. See

1
Lombard v. Colo. Outdoor Educ. Ctr., Inc., 187 P.3d 565, 575 (Colo.

2008). In such cases, determining whether the landowner breached

a duty of reasonable care to the injured licensee may hinge on

which version of the ordinance applies. See id.

¶4 We first consider which version of the local fire safety

ordinance applies in this premises liability case arising from a fire

at a leased dwelling. The ordinance has been amended at least

twice since the dwelling’s construction, so the applicable ordinance

could be the one in effect at the time of construction, the one in

effect at the time the landowner leased the subject premises to the

tenant, or the one in effect at the time the subject children were

injured. We conclude that, under the facts of this case, the

applicable ordinance is the one in effect at the time the children

were injured.

¶5 Second, we interpret the edition of the International Fire Code

(the IFC) embodied in the applicable ordinance. No reported

decision in Colorado has interpreted a provision of the IFC, and our

interpretation applies to the edition of the IFC in effect in Durango

today. We hold that, under section 1103.8.1 of the 2012 edition of

the IFC — the applicable edition — landowners are not required to

2
comply with the smoke alarm requirements specified in the 2012

IFC so long as (1) a building code was in effect at the time of

construction; (2) such code required smoke alarms; and (3) smoke

alarms complying with those requirements were already provided in

the dwelling.

¶6 Our analysis leads to the conclusion that the trial court erred

by instructing the jury on an earlier version of the ordinance than

the one in effect at the time the plaintiff children were injured.

Accordingly, we reverse the judgment entered in favor of the

children and remand the case to the trial court for further

proceedings consistent with this opinion.

¶7 We also address whether, under the facts of this case, the

property manager’s authorized agent was a “landowner” for

purposes of the Act and review the children’s request for attorney

fees under section 13-17-102(2), C.R.S. 2024. We decline to

consider the other issues presented in this appeal because they are

unlikely to arise in the same manner on remand.

3
I. Background

A. Facts

¶8 In the early morning hours of June 14, 2017, fire swept

through the two-story residential unit at the Tercero Townhomes

(the townhomes) in Durango that Hilda Picasso (aunt) leased. At

the time of the fire, aunt’s sister Grisela Picasso (mother) and

mother’s minor children Rivers Picasso Martinez and Ira Picasso

Martinez (the children) were staying in the unit. Mother and the

children were asleep in an upstairs bedroom when mother awoke to

heat and smoke. Mother and the children were unable to escape

through the bedroom because the flames had reached the bedroom

door.

¶9 Mother pushed the children out the bedroom window before

escaping through it herself. The children sustained physical and

psychological injuries as a result of the incident.

¶ 10 Several other individuals were also asleep in the unit when the

fire broke out. None of them who testified at trial said they heard a

smoke alarm in the unit that night.

4
B. Procedural History

¶ 11 Anthony Martinez (father), in his capacity as the children’s

father and next friend, sued Cast, LLC, the owner of the townhomes

at the time of the fire; Caroni Adams, Inc. (CAI), the townhomes’

property manager; and Carolyn Caroni Adams (Ms. Adams), in her

capacity as an owner and agent of Cast and CAI (collectively, the

Adams parties), under the Act to recover damages for the children’s

injuries. The children, through father, alleged that the Adams

parties were liable to the children under the Act because the unit

“did not have the required number of operational smoke alarms.”

(We refer to the plaintiffs as “the children,” even though father

prosecuted this case on their behalf.)

¶ 12 At trial, witnesses presented conflicting testimony on whether

the unit had one or two smoke alarms. The parties did not dispute

that one smoke alarm hung on the ceiling in the hallway between

the two upstairs bedrooms. Most of the witnesses said it was the

only smoke alarm in the unit.

¶ 13 The children’s lawyer presented testimony from a fire safety

expert that the upstairs smoke alarm was likely installed in 1979,

when the unit was constructed. The expert said that, at the time of

5
the fire, the smoke alarm had exceeded its recommended life of ten

years by several decades.

¶ 14 After the presentation of evidence, the court instructed the

jury that a Durango ordinance in effect at the time of the fire

required that “occupancies” such as the unit be furnished with four

smoke alarms.

¶ 15 The jury found the Adams parties liable for the children’s

injuries. The court entered a judgment in favor of the children, and

against the Adams parties, jointly and severally, in the principal

amount of $2,483,317.16.

¶ 16 As relevant here, the Adams parties collectively contend that

the court provided an incorrect ordinance as evidence of the

applicable standard of care. Ms. Adams and CAI jointly appeal the

court’s determination that Ms. Adams is a landowner under the Act.

¶ 17 We reverse and remand the case to the trial court because the

court instructed the jury on a Durango ordinance that was not

germane to determining the landowners’ standard of care. In

addition, we conclude that the trial court did not err by finding that

Ms. Adams was a “landowner” under the Act and decline the

children’s request for an award of their attorney fees.

6
II. The Act

¶ 18 “The General Assembly enacted the [Act] to ‘establish a

comprehensive and exclusive specification of the duties landowners

owe to those injured on their property.’” Warembourg v. Excel Elec.,

Inc., 2020 COA 103, ¶ 36, 471 P.3d 1213, 1221 (quoting Vigil v.

Franklin, 103 P.3d 322, 328 (Colo. 2004)); see also Wycoff, 251 P.3d

at 1265.

¶ 19 The Act provides, “In any civil action brought against a

landowner by a person who alleges injury occurring while on the

real property of another and by reason of the condition of such

property, or activities conducted or circumstances existing on such

property, the landowner is liable only as provided in” section

13-21-115(4). § 13-21-115(3). (The Colorado General Assembly

amended the Act in 2022. See Ch. 75, sec. 2, § 13-21-115, 2022

Colo. Sess. Laws 383. In doing so, it renumbered several of the

Act’s subsections. Because the amendments did not substantively

change the relevant portions of the Act, we cite the current version.)

¶ 20 Section 13-21-115(4) “outlines the respective duties that a

landowner owes to trespassers, invitees, and licensees and provides

that a breach of those duties may result in liability for damages

7
caused.” Warembourg, ¶ 38, 471 P.3d at 1221 (quoting Lombard,

187 P.3d at 574). “A landowner owes the greatest duty of care to an

invitee, a lesser duty to a licensee, and the least duty to a

trespasser.” Id. at ¶ 39, 471 P.3d at 1221.

¶ 21 As explained above, a “licensee” is “a person who enters or

remains on the land of another for the licensee’s own convenience

or to advance the licensee’s own interests, pursuant to the

landowner’s permission or consent,” and social guests are

“licensees.” § 13-21-115(7)(c). Because the parties do not challenge

the court’s finding that the children were licensees, we express no

opinion on their status for purposes of the Act.

¶ 22 “A licensee may only recover damages caused . . . [b]y the

landowner’s unreasonable failure to exercise reasonable care with

respect to dangers created by the landowner that the landowner

actually knew about.” § 13-21-115(4)(b)(I). (Our opinion should not

be read to mean that evidence of a landowner’s failure to exercise

reasonable care, without more, is sufficient to prove a claim under

the Act; the licensee must also present evidence regarding “the

remaining statutory requirements, namely the landowner’s actual

8
or constructive knowledge of the danger, proximate cause, and

damages.” Lombard, 187 P.3d at 575.)

III. Evidence of the Applicable Standard of Care

¶ 23 The parties dispute the meaning of the language in Durango’s

fire safety ordinance (the Durango fire code) that addresses the

requirements for smoke alarms in buildings such as the unit.

Specifically, they disagree about which smoke alarm requirements

were relevant to the case and, thus, which requirements provided

relevant evidence of whether the Adams parties exercised

reasonable care.

¶ 24 The Adams parties contend that the court instructed the jury

on the incorrect standard of care by providing it with a version of

the Durango fire code that required a greater number of smoke

alarms than were installed in the unit. We agree.

A. Standard of Review

¶ 25 “Trial courts have a duty to correctly instruct juries on all

matters of law,” and appellate courts review de novo whether a

particular jury instruction correctly stated the law. Day v. Johnson,

255 P.3d 1064, 1067 (Colo. 2011). An instructional error is

harmless unless it prejudiced a party’s substantial rights.

9
Bullington v. Barela, 2024 COA 56, ¶ 18, 555 P.3d 102, 106. “A

party’s substantial rights are prejudiced when the jury ‘might have

answered differently if a proper instruction had been given.’” Id.

(quoting Banning v. Prester, 2012 COA 215, ¶ 10, 317 P.3d 1284,

1287).

¶ 26 Under the Act, a landowner breaches the standard of care by

“unreasonabl[y] fail[ing] to exercise reasonable care.”

§ 13-21-115(4)(b)(I). “[R]easonable care is measured by what a

person of ordinary prudence would or would not do under the same

or similar circumstances.” Lombard, 187 P.3d at 574. To prove

that a landowner failed to exercise reasonable care, a plaintiff may

present “evidence that the landowner violated a statute or

ordinance.” Id. at 575. This is so because “a person of ordinary

prudence would generally follow the law.” Id. at 574. A plaintiff

may also introduce evidence that a defendant failed to comply with

a municipal safety code or regulation to establish a breach of the

applicable standard of care. See Scott v. Matlack, Inc., 39 P.3d

1160, 1167 (Colo. 2002).

¶ 27 In such cases, the court generally considers the version of the

code or regulation in effect at the time of the plaintiff’s injury. See

10
Bennett v. Greeley Gas Co., 969 P.2d 754, 760 (Colo. App. 1998)

(holding that a relevant safety code or regulation may be admissible

if it “gives some indication of the standard of care at the time of the

alleged negligence”); see also Scott, 39 P.3d at 1167 (explaining that,

to be admissible as evidence of the standard of care, a safety statute

“must be relevant”). But see Lombard, 187 P.3d at 575 (applying a

municipal building code in effect at the time of construction to

determine if a condition was dangerous when built).

¶ 28 “Interpretation of a municipal ordinance involves a question of

law subject to de novo review.” MDC Holdings, Inc. v. Town of

Parker, 223 P.3d 710, 717 (Colo. 2010). We follow the “ordinary

rules of statutory construction” when interpreting a city code.

Alpenhof, LLC v. City of Ouray, 2013 COA 9, ¶ 10, 297 P.3d 1052,

1055.

¶ 29 “Our principal goal in interpreting . . . local government

enactments is to determine and effectuate the intent of those who

adopted those measures.” Kulmann v. Salazar, 2022 CO 58, ¶ 16,

521 P.3d 649, 653. “To do so, we look first to the language

employed, giving words and phrases their plain and ordinary

meanings.” Id. “In addition, we look to the entire legislative scheme

11
in order to give consistent, harmonious, and sensible effect to all of

its parts, and we avoid constructions that would render any words

or phrases superfluous or lead to illogical or absurd results.” Id.

“[W]e will not add words to a statute or subtract words from it.”

Miller v. Crested Butte, LLC, 2024 CO 30, ¶ 23, 549 P.3d 228, 234.

¶ 30 “If the language of the measure is unambiguous, then we

apply it as written and need not resort to other tools of

construction.” Kulmann, ¶ 17, 521 P.3d at 653. In addition, “if the

statutory language is clear and unambiguous, the language should

not be subjected to a strained or forced interpretation.” City of

Colorado Springs v. Securcare Self Storage, Inc., 10 P.3d 1244, 1249

(Colo. 2000).

B. The Regulation of Smoke Alarms

¶ 31 Local governments throughout the country can look to model

codes for guidance when considering their own ordinances and

statutes governing smoke alarms and other matters affecting the

structures in their communities.

¶ 32 The International Code Council (ICC), which was founded in

1994 to “develop[] a single set of national model construction

codes,” ICC, Who We Are, https://perma.cc/XN22-PN2K,

12
promulgates numerous model codes, including model building

codes, residential codes, and mechanical codes. ICC, The

International Codes (I-Codes), https://perma.cc/4SGH-GSAR. The

IFC is one of those codes. The ICC published the first IFC in 2000.

It published and continues to publish new editions of the IFC every

three years. ICC, 2015 IFC, Preface, https://perma.cc/8GUJ-255L.

¶ 33 The IFC separates its rules governing “fire alarm and detection

systems,” id. § 907, for “occupancies” such as the unit into two

categories: (1) fire alarm systems and (2) single- and

multiple-station smoke alarms. Id. § 907.2.9. The IFC generally

requires installation of a fire alarm system in buildings more than

three stories in height or with more than sixteen dwelling or

sleeping units, subject to several exceptions not relevant here.

Id. § 907.2.9.1. All other occupancies are the subject of the IFC’s

single- and multiple-station smoke alarm rules.

¶ 34 The Durango City Council (the City Council) has adopted

various editions of the IFC.

13
C. The Smoke Alarm Requirements
Applicable to the Unit

¶ 35 Because the parties disagree as to which Durango fire code

ordinance provides evidence of the applicable standard of care, we

provide a brief history of the City Council’s adoption of ordinances

governing smoke alarms.

¶ 36 Construction of the unit began in 1978 and concluded in

1979. For purposes of the IFC, the unit was an “R-2” occupancy,

with a kitchen and living room on the first floor and two bedrooms

on the second floor. See ICC, 2012 IFC § 202, at 36,

https://perma.cc/Z5ET-LB5R (An “R-2 occupancy” is a residential

occupancy “containing sleeping units or more than two dwelling

units where the occupants are primarily permanent in nature,

including: [a]partment houses . . . .”). Because of the unit’s size, it

was not required to contain a fire alarm system; rather, it was

subject to Durango’s regulations concerning single- or multiple-

station smoke alarms.

¶ 37 When the unit was constructed, the applicable Durango

building code was the 1976 Uniform Building Code (1976 UBC),

which the City Council adopted in 1977. Durango, Colo., Amended

14
Ordinance No. 1239 (1977). The 1976 UBC required that smoke

alarms “be mounted on the ceiling or wall at a point centrally

located in the corridor or area giving access to rooms used for

sleeping purposes.” Int’l Conf. of Bldg. Offs., 1976 UBC § 1310(a),

at 90-91, https://perma.cc/ST2S-D5P9.

¶ 38 In 2005, the City Council adopted the 2003 edition of the IFC

through Ordinance No. O-2005-33. Section 907.2.10.1.2 of the

2003 IFC required that smoke alarms be installed and maintained

in R-2 occupancies (1) outside each separate sleeping area; (2) in

each room used for sleeping purposes; and (3) in each story within

a dwelling unit. ICC, 2003 IFC § 907.2.10.1.2, at 78-79,

https://perma.cc/SH65-FK4L. Section 907.3.2.1 of the 2003 IFC

specified that existing buildings “not already provided with single-

station smoke alarms” must be provided with them consistent with

the foregoing standard (the 2003 exception). Id. § 907.3.2.1, at 82.

¶ 39 Aunt entered into her lease agreement for the unit with CAI in

May 2014. Because the 2003 IFC was Durango’s fire code from

2005 until January 1, 2016, it was the edition of the IFC in effect in

Durango when aunt signed her lease.

15
¶ 40 On December 1, 2015, the City Council adopted the 2012 IFC,

effective January 1, 2016. Durango, Colo., Ordinance No.

O-2015-30. Section 907.2.11.2 of the 2012 IFC contained the same

requirements for the installation of smoke alarms in R-2

occupancies as did the 2003 IFC. 2012 IFC § 907.2.11.2, at 117-

18.

¶ 41 However, in a new chapter entitled “Construction

Requirements for Existing Buildings,” the 2012 IFC said, as

relevant here, that additional smoke alarms were not required when

“the code that was in effect at the time of construction required

smoke alarms and smoke alarms complying with those

requirements are already provided” (the 2012 exception).

Id. § 1103.8.1, at 185 (emphasis added). Because the 2012 IFC was

in effect from January 1, 2016, through the end of 2017, it was the

edition of the IFC in effect in Durango at the time the children were

injured.

¶ 42 The below table summarizes the smoke alarm requirements for

R-2 occupancies in Durango at the times relevant to this case:

16
Years Relevance Code Requirement

1978- Construction 1976 UBC A smoke alarm centrally
2005 located in the corridor giving
access to rooms used for
sleeping purposes

2006-15 Lease 2003 IFC A smoke alarm outside each
executed sleeping area, inside each
bedroom, and on each story,
with an exception for
existing buildings “already
provided with” smoke alarms

2016-17 Fire 2012 IFC Same requirement as 2003
IFC, with an exception for
existing buildings “where the
code that was in effect at the
time of construction”
required smoke alarms and
the building complied with
that code

D. Additional Procedural History

¶ 43 Before trial, the court granted summary judgment for the

Adams parties, concluding that the children failed to establish “but

for” causation. The children appealed. A division of this court

reversed and remanded, holding that the issue of “but for”

causation was triable. Martinez v. Cast, LLC, slip op. at 7-9 (Colo.

App. No. 21CA0193, June 9, 2022) (not published pursuant to

C.A.R. 35(e)). As relevant here, the division also directed the court

17
to determine which “code” applied to the children’s claims. Id. at

17-19, 21. On remand, the children moved for a determination of a

question of law regarding which “code” was relevant to determining

the applicable standard of care.

¶ 44 The court ruled on that motion in an order dated June 7,

2023. It appeared to conclude that the 2012 IFC — the edition of

the IFC in effect at the time the children were injured — was

relevant evidence of the applicable standard of care. The court

found that the phrase “the code that was in effect at the time of

construction” in the 2012 exception only referred to earlier editions

of the IFC, and not to earlier editions of non-IFC codes, such as

building codes. Thus, the court reasoned, the 2012 exception did

not apply because the unit complied with the 1976 UBC, but not

with an edition of the IFC predating the 2012 edition. The court

made this finding for two reasons: (1) “the structure and wording of

the IFC codes (both 2003 and 2012 versions)” and (2) “public

policy.”

¶ 45 In considering the structure and text of the different editions

of the IFC, the court reasoned that, when the IFC referred to

non-IFC codes, it identified them by name. The IFC otherwise

18
referred to itself as “this code.” According to the court, if the IFC

drafters intended that the 2012 exception apply to any code

containing smoke alarm requirements, such as the 1976 UBC, the

IFC would have referenced such codes by name.

¶ 46 The court also noted that, as a matter of public policy, a broad

reading of the 2012 exception would be “inconsistent with the

general purpose of holding builders accountable for failing to meet

the minimum standard of care.” The court said that concluding “a

builder can construct a building and, without consequence, never

make any safety upgrades in fifty years so long as it was in

compliance with any code in place fifty years ago” would be

“absurd” and “unreasonable.”

¶ 47 But later in its June 7 order, the court contradicted its earlier

implication that the 2012 IFC was relevant evidence of the standard

of care by finding that the Adams parties’ alleged negligence

occurred in 2014, when aunt signed her lease agreement, and not

in 2017, when the fire occurred. It found that the 2003 IFC was the

governing IFC edition when aunt signed her lease and, because the

2003 IFC “superseded” the 1976 UBC, the Adams parties were

required to comply with the smoke alarm requirements contained in

19
the 2003 IFC before renting the unit to aunt. According to the

court, their failure to do so was “the alleged negligence leading to

the harm to [the children].” Thus, the court concluded that the

2003 IFC was relevant evidence of the standard of care.

¶ 48 At trial, the court provided the jury with an instruction

quoting section 907.2.10.1.2 of the 2003 IFC. Under that section,

four smoke alarms would have been required in the unit: one on the

first floor, one in each bedroom, and one outside the bedroom

doors. The court did not, however, instruct the jury on the 2003

exception, which said that existing buildings “not already provided

with” smoke alarms must be furnished with them according to

section 907.2.10.1.2. 2003 IFC § 907.3.2.1, at 82 (emphasis

added).

E. The Adams Parties Did Not Abandon Their Argument
Regarding the Applicable Fire Code

¶ 49 As an initial matter, the children assert that the Adams parties

“abandoned” their argument regarding the applicable fire code

because the Adams parties said, in a motion filed before the first

appeal in the case, that they had no intention of arguing that the

20
1976 UBC “is the code the jury is to apply to the number of smoke

detectors required.” We disagree.

¶ 50 Nowhere did the Adams parties assert that they were

abandoning their argument that the version of the Durango fire

code in effect at the time the children were injured was the relevant

evidence of the standard of care. See People v. Rediger, 2018 CO

32, ¶ 39, 416 P.3d 893, 902 (explaining that waiver is the

intentional relinquishment of a known right or privilege); United

States v. Adigun, 703 F.3d 1014, 1021 (7th Cir. 2012) (noting that a

party waives an issue by making an “intentional (and often

strategic) choice” to remove it from controversy).

F. The Court Erroneously Provided the Jury with Language from
an Inapplicable Edition of the IFC

¶ 51 In their answer brief, the children contend that the court

properly instructed the jury with the 2003 IFC. Alternatively, they

assert that, if the 2012 IFC applies, we should follow the district

court’s interpretation of the 2012 exception. Thus, we must first

determine which edition of the IFC provided relevant evidence of the

standard of care, and we conclude that the 2012 IFC did so. We

next consider the meaning of the 2012 exception and conclude that

21
it refers to any code, not solely any edition of the IFC, governing

smoke alarms in effect at the time of construction. Finally, we

address the implications of our interpretation for the relevant

standard of care in this case.

1. The Applicable Edition of the IFC Was the One in Effect
in Durango at the Time the Children Were Injured

¶ 52 The court erred by concluding that the 2003 IFC applied to the

determination of the applicable standard of care because it was the

“code” in effect at the time of the “alleged negligence,” which the

court said was the Adams parties’ failure to install the requisite

number of smoke alarms before they leased the unit to aunt.

¶ 53 The children did not allege that the dangerous condition

existed when aunt signed her lease for the unit. Instead, they

asserted that the determination of whether there was a dangerous

condition at the unit must focus on the conditions on the night of

the fire. See § 13-21-115(4)(b)(I) (“A licensee may only recover

damages caused . . . [b]y the landowner’s unreasonable failure to

exercise reasonable care . . . .”) (emphasis added). As a matter of

logic, the children’s claims under the Act were premised on a

dangerous condition that existed at the time they were injured and

22
not on dangerous conditions on an earlier date. Thus, we must

consider evidence of the standard of care — the smoke alarm

requirements in Durango — at the time of the children’s injuries.

¶ 54 Even if we were to conclude that the lease execution date was

relevant to determining the applicable standard of care at the time

of the “alleged negligence,” the court overlooked the critical fact

that, although aunt executed her initial lease for the unit in 2014,

she renewed the lease in 2016, when the 2012 IFC was in effect in

Durango.

¶ 55 We recognize that, in Lombard, 187 P.3d at 575, the Colorado

Supreme Court referenced the municipal building code in effect at

the time of construction as evidence of whether a permanent ladder

giving access to a loft was a dangerous condition. In that case,

which the plaintiff brought under the Act, the parties contested

whether the plaintiff could point to such building code as evidence

that the defendant failed to exercise reasonable care. Id. at 568.

But unlike in this case, the parties in Lombard did not contest

which version of the ordinance provided evidence of the standard of

care at the time the plaintiff was injured. Id. at 575. Thus,

Lombard did not address the question before us.

23
¶ 56 Thus, the 2012 IFC was the edition of the IFC relevant to the

children’s premises liability claim because it was the edition in

effect in Durango when the children were injured.

2. The 2012 Exception Refers to Any Code —
Not Solely Any Edition of the IFC —
Governing Smoke Alarms in Effect at the Time of Construction

¶ 57 We must next determine the meaning of the 2012 exception —

that the smoke alarm requirements in the 2012 IFC did not apply to

existing buildings when (1) a code “was in effect at the time of

construction”; (2) such code “required smoke alarms”; and (3)

“smoke alarms complying with those requirements are already

provided” in the building. 2012 IFC § 1103.8.1, at 185.

a. The Language of the 2012 Exception

¶ 58 We conclude that “the code that was in effect at the time of

construction” unambiguously means any code — not solely any

edition of the IFC — containing a smoke alarm requirement that

was in effect in the subject jurisdiction when the occupancy was

constructed. The 2012 exception contains no qualifier suggesting

that the code in effect at the time of construction must be an earlier

IFC edition. Because the language of the 2012 exception is

unambiguous, it should not be “subjected to a strained or forced

24
interpretation.” City of Colorado Springs, 10 P.3d at 1249. And we

will not add words to the 2012 exception that do not plainly appear

in it. See Miller, ¶ 23, 549 P.3d at 234.

¶ 59 The 2012 exception’s reference to a “code” that “required

smoke alarms” would be superfluous if “code” only meant “edition

of the IFC,” as every IFC edition required smoke alarms. The

inclusion of the qualifier “required smoke alarms” makes sense only

if some “codes” did not require smoke alarms, and the 2012

exception therefore needed to distinguish between codes that did

and did not require smoke alarms. This distinction tells us that

“code” encompasses types of codes, such as building codes, that did

not uniformly require the installation of smoke alarms in new

buildings. See Indus. Claim Appeals Off. v. Town of Castle Rock,

2016 CO 26, ¶ 15, 370 P.3d 151, 155 (noting that courts avoid

interpretations of statutes that render provisions superfluous).

¶ 60 Accordingly, the unambiguous language of the 2012 exception

establishes that “code” means any code that required buildings to

contain smoke alarms at the time of construction and not merely

earlier IFC editions.

25
b. The Text Surrounding the 2012 Exception and
the Accompanying Commentary

¶ 61 The children assert that we cannot determine whether the

2012 exception applies to this case without also examining the text

surrounding the 2012 exception and the accompanying

commentary. See Bryant v. Cmty. Choice Credit Union, 160 P.3d

266, 274 (Colo. App. 2007) (“The plainness or ambiguity of

statutory language is determined by reference to the language itself,

the specific context in which that language is used, and the broader

context of the statute as a whole.” (quoting Robinson v. Shell Oil Co.,

519 U.S. 337, 341 (1997))); People v. Bagwell, 2022 COA 44, ¶ 19,

514 P.3d 953, 958 (explaining that, where no case has interpreted a

Colorado statute premised on a model code, we refer to the model

code and its commentary for guidance). The children argue that the

surrounding text and commentary support their contention that the

2012 exception does not exempt existing buildings from the 2012

IFC’s substantive smoke alarm requirements. We disagree.

¶ 62 As we explain below, the text surrounding and the

commentary to the 2012 exception undermine the children’s — and

the court’s — reading of the 2012 exception to mean that “the code

26
that was in effect at the time of construction” only means the IFC

edition in effect at the time of construction.

¶ 63 The 2012 IFC refers to itself as “this code.” See, e.g., 2012 IFC

§ 101.1, at 1 (“These regulations shall be known as the Fire Code of

[NAME OF JURISDICTION], hereinafter referred to as ‘this code.’”).

The IFC generally refers to past versions of itself by identifying the

year of the edition. See, e.g., 2012 IFC, Preface, at iii (“This 2012

edition presents the code as originally issued, with changes

reflected in the 2003, 2006 and 2009 editions . . . .”); id. at v (“Solid

vertical lines in the margins within the body of the code indicate a

technical change from the requirements of the 2009 edition.”).

These references demonstrate that the drafters knew how to limit

the 2012 exception to buildings that complied with earlier IFC

editions if they chose to do so.

¶ 64 The court was correct that the IFC occasionally refers to

non-IFC codes by name. But we do not agree with the court’s

conclusion that, if the drafters intended for the 2012 exception to

apply to non-IFC codes, such as the 1976 UBC, the drafters would

have referenced those codes by name, as they had in other parts of

the 2012 IFC. Many of the pre-IFC codes containing smoke alarm

27
requirements were unique to specific jurisdictions. Given that the

IFC is a model fire code, adopted in numerous jurisdictions, we do

not see how the drafters could have feasibly identified by name all

the non-IFC codes it intended to include in the 2012 exception.

Instead, the drafters chose an unambiguous shorthand: “the code

that was in effect at the time of construction.” That shorthand

makes sense, and we will not subject it to a strained interpretation

that yields a different result.

¶ 65 In addition, the IFC drafters’ commentary to the 2012

exception undercuts the children’s and the court’s reading of the

2012 exception. The commentary explains:

Three exceptions are also provided to address
possible scenarios where smoke alarms have
already been installed but the installation does
not meet the current code requirements,
recognizing that the intent of the code is to
permit existing smoke alarm installations to
continue unchanged where they meet the code
that was in effect at the time they were
installed. Exception 1 indicates that smoke
alarms which have been installed and
maintained in accordance with the applicable
code at the time of construction can continue
unchanged. . . . In summary, this section
requires the installation of smoke alarms in
Group . . . R occupancies that do not currently
have any smoke alarms. It does not require
compliance with the current smoke alarm

28
requirements if the building already has smoke
alarms that meet requirements that were
applicable when they were installed. The focus
here is not to have the owner replace or revise
their smoke alarms any time the code
requirements for new construction change.

ICC, 2012 IFC Code and Commentary § 1103.8.1, at 353 (emphases

added).

¶ 66 These materials support our conclusion that “the code that

was in effect at the time of construction” means any earlier code

containing a smoke alarm requirement and is therefore not limited

to earlier IFC editions. They establish that the drafters of the 2012

exception were concerned with buildings that were not required to

have any smoke alarms when constructed.

¶ 67 Thus, limiting “the code that was in effect at the time of

construction” to prior IFC editions would frustrate the drafters’

intent to “permit existing smoke alarm installations to continue

unchanged where they meet the code that was in effect at the time

they were installed.” Id. Of course, vast numbers of buildings were

constructed before 2000, when the first IFC was promulgated. The

court’s interpretation would require all those buildings to be

retrofitted, at unimaginable expense, to comply with the smoke

29
alarm requirements in the IFC edition then in effect in the

applicable jurisdiction. Most significantly, this reading of the 2012

exception would be directly counter to the drafters’ intent expressed

in its plain language.

c. The Children’s Further Arguments Regarding
the 2012 Exception

¶ 68 The children raise two further arguments supporting the

court’s interpretation of the 2012 exception: one regarding the

exception’s formatting and one resting on public policy

considerations. We address and reject them in turn.

¶ 69 We are not persuaded by the children’s contention that the

2012 exception only applies to sections 1103.8.2 and 1103.8.3 of

the 2012 IFC, rather than to section 1103.8.1, under which it is

nested. An image of the 2012 exception’s placement within the

2012 IFC is instructive:

30
Image 1: The image shows general rules titled in bolded text with
exceptions to each general rule indented underneath. The
challenged exception is circled in red font, and it is indented under
section 1103.8.1. Section 1103.8.2 begins underneath and is left
justified with a bolded title. It is followed by its own set of indented
exceptions.

¶ 70 The formatting of sections 1103.8.1 and 1103.8.2 and the fact

that section 1103.8.2 contains separate exceptions nested

underneath it undermine the children’s argument. Accordingly, the

2012 exception clearly is a carveout from section 1103.8.1’s

31
language that “[e]xisting . . . R occupancies shall be provided with

single-station smoke alarms in accordance with Section

907.2.11[’s]” requirement that smoke alarms be installed and

maintained (1) outside each separate sleeping area; (2) in each room

used for sleeping purposes; and (3) in each story within a dwelling

unit.

¶ 71 Finally, the children question, as a matter of public policy, the

wisdom of excepting from the IFC’s smoke alarm requirements

those buildings that only complied with earlier codes in effect in the

jurisdiction at the time of construction. Although the children’s

public policy concerns may have merit, they are a matter for the

City Council, and not this court, to address. “[C]ourts must avoid

making decisions that are intrinsically legislative. It is not up to the

court to make policy or to weigh policy.” Town of Telluride v. Lot

Thirty-Four Venture, L.L.C., 3 P.3d 30, 38 (Colo. 2000). We must

interpret the 2012 exception as the City Council adopted it,

consistently with its unambiguous language. See Migoya v.

Wheeler, 2024 COA 124, ¶ 55, ___ P.3d ___, ___ (“[W]e must apply

[statutes] as drafted. Our role is not to second-guess [legislative

bodies’] policy decisions.”).

32
¶ 72 In sum, we hold that the 2012 IFC carved out an exception

from its smoke alarm standards for any building that complied with

the smoke alarm standards in effect at the time of its construction,

whether those standards appeared in an IFC edition or in another

type of code, so long as those standards required the installation of

smoke alarms.

3. The 2012 Exception and the 1976 UBC Provide
Relevant Evidence of the Applicable Standard of Care

¶ 73 As explained above, the version of the Durango fire code in

effect at the time the children were injured — the 2012 IFC —

carved out an exception to the IFC’s smoke alarm requirements for

buildings that complied with the smoke alarm requirements

embodied in the code in effect when the building was constructed.

¶ 74 The 1976 UBC was in effect in Durango when the unit was

constructed. The 1976 UBC required that a smoke alarm be

“mounted on the ceiling or wall at a point centrally located in the

corridor or area giving access to rooms used for sleeping purposes.”

UBC § 1310(a), at 90-91. The parties do not dispute that, when it

was constructed, the unit complied with the 1976 UBC’s smoke

alarm requirements.

33
¶ 75 Thus, the code sections providing relevant evidence of the

standard of care were the 2012 exception and section 1310(a) of the

1976 UBC. For these reasons, we hold that the court erred by

providing the jury with an instruction quoting section 907.2.10.1.2

of the 2003 IFC. See Bennett, 969 P.2d at 760; Scott, 39 P.3d at

1167. Because “the jury ‘might have answered differently if a

proper instruction had been given,’” Bullington, ¶ 18, 555 P.3d at

106 (citation omitted), the court’s instructional error substantially

affected the Adams parties’ substantial rights and, therefore, was

not harmless.

IV. Ms. Adams’s Status as a Landowner

¶ 76 Next, we address an issue likely to recur in the event of a

retrial: CAI and Ms. Adams’s contention that the court erred by

finding that she was a “landowner” under the Act.

A. Applicable Law and Standard of Review

¶ 77 “An injured person may bring a claim under the [Act] only

against a ‘landowner.’” Lopez v. Trujillo, 2016 COA 53, ¶ 34, 399

P.3d 750, 756 (quoting § 13-21-115(3)), aff’d sub nom. N.M. v.

Trujillo, 2017 CO 79, 397 P.3d 370. “[T]he general assembly defined

‘landowner’ quite broadly . . . .” Pierson v. Black Canyon

34
Aggregates, Inc., 48 P.3d 1215, 1219 (Colo. 2002). The term

“encompasses both: (1) ‘an authorized agent or a person in

possession of real property’; and (2) ‘a person legally responsible for

the condition of real property or for the activities conducted or

circumstances existing on real property.’” Jordan v. Panorama

Orthopedics & Spine Ctr., PC, 2015 CO 24, ¶ 22, 346 P.3d 1035,

1041 (quoting what is now section 13-21-115(7)(b)); see also

Henderson v. Master Klean Janitorial, Inc., 70 P.3d 612, 614 (Colo.

App. 2003) (“These definitions must be read in the disjunctive.”).

“Both statutory definitions confer landowner status on those who

are responsible for the conditions, activities, or circumstances

existing on real property.” Jordan, ¶ 22, 346 P.3d at 1041. A

person need not hold title to property to be considered a

“landowner.” Lopez, ¶ 34, 399 P.3d at 756.

¶ 78 In considering the parties’ arguments, we focus on the first

statutory definition of a landowner: an authorized agent or a person

in possession of real property.

¶ 79 “An agent is one who acts for or in the place of another by

authority from him, or one who is entrusted with the business of

another.” Digit. Landscape Inc. v. Media Kings LLC, 2018 COA 142,

35
¶ 76, 440 P.3d 1200, 1212 (quoting Governor’s Ranch Pro. Ctr., Ltd.

v. Mercy of Colo., Inc., 793 P.2d 648, 651 (Colo. App. 1990)). “As an

inanimate entity, a corporation must act through agents.” Genova

v. Longs Peak Emergency Physicians, P.C., 72 P.3d 454, 462 (Colo.

App. 2003); see also Colo. Coffee Bean, LLC v. Peaberry Coffee Inc.,

251 P.3d 9, 29 (Colo. App. 2010).

¶ 80 “[A] person ‘in possession of’ land is one who occupies the land

with intent to control it, although not necessarily to the exclusion of

all others.” Jordan, ¶ 23, 346 P.3d at 1041; Pierson, 48 P.3d at

1220. In holding that exclusive possession is not required, the

Pierson court cited the Restatement (Second) of Torts (Am. L. Inst.

1965), which provided that a possessor of land includes “a person

who is entitled to immediate occupation of the land, if no other

person is in possession.” 48 P.3d at 1220 (quoting Restatement

(Second) of Torts § 328E).

¶ 81 A landlord is a “person in possession of real property” — and

thus a “landowner” — if, as here, the lease for the property provides

that the tenant “surrendered [her] right to exclusive possession and

control over the property in such a way as to share control” with the

landlord; the landlord “reserved the power or authority to manage,

36
superintend, direct, or oversee repairs on the premises”; and there

is no evidence of “a pattern” that tenant maintained and repaired

the property without notice to the landlord or that the landlord

stopped inspecting the property. Nordin v. Madden, 148 P.3d 218,

220-21 (Colo. App. 2006).

¶ 82 “[T]he covenant to repair gives the landlord a right to enter the

premises, and hence amounts to a retention of a degree of control.”

Id. at 220 (quoting Glen Weissenberger & Barbara B. McFarland,

The Law of Premises Liability § 9.8, at 245 (3d ed. 2001)). “On the

other hand, when a landowner transfers complete control of the

premises to a lessee, that landowner is no longer a person in

possession for purposes of the statute.” Pierson, 48 P.3d at 1220.

¶ 83 “Whether a party is a landowner within the meaning of the

[Act] is a mixed question of fact and law.” Lopez, ¶ 33, 399 P.3d at

756. “We review a court’s findings of historical fact for clear error”

and “review de novo the ultimate legal conclusion that a party is a

landowner.” Id.

37
B. Ms. Adams Is a Landowner within the Meaning of the Act

¶ 84 We conclude that Ms. Adams had a sufficient possessory

interest in the unit to qualify as a landowner under the Act. We

reach this conclusion for two reasons.

¶ 85 First, Ms. Adams was CAI’s authorized agent. Ms. Adams

purchased the unit in 2014 and then quitclaimed her interest in the

unit to Cast. That same year, Cast executed a management

agreement with “Caroni Adams, Inc. d/b/a The Property Manager,”

authorizing it to “lease, operate and manage” the unit on Cast’s

behalf. Ms. Adams signed the agreement on behalf of CAI in her

capacities as its owner, real estate broker, and president. In

addition, Ms. Adams testified that she executed all the leases for,

and inspected, the properties that CAI managed. We conclude that

this evidence was sufficient to demonstrate that Ms. Adams acted

with authority as CAI’s agent.

¶ 86 Second, CAI was in possession of the unit within the meaning

of the Act. The lease agreement between aunt and CAI provided, in

relevant part:

• “If the premises are left vacant or [aunt] is evicted and

any part of the rent herein reserved be unpaid, then [CAI]

38
may . . . without terminating this lease, retake

possession of the said premises and rent the same.”

• “[Aunt] shall report problems and repairs needed

promptly within 24 hours to [CAI].”

• “[Aunt] shall permit [Cast], [its] Agent or [CAI] to enter the

premises at reasonable times for the purpose of

inspecting said property; provided, however, that [Cast or

CAI] shall give reasonable notice to [aunt] of [its] desire to

inspect the premises under the terms of this paragraph,

except in case of an emergency situation which threatens

the property . . . .”

• “[CAI] shall have the right to show the premises to

prospective tenants during the last month of this

tenancy.”

• “[CAI] and/or [Cast] may show the property to

purchasers, mortgagees, or appraisers with reasonable

notice.”

While the lease generally provided that aunt was responsible for

routine maintenance of the unit, testimony at trial showed that CAI

39
performed repairs to the unit, as well as the other properties it

managed.

¶ 87 The record establishes that CAI retained control over the unit

by nature of its right to assume immediate possession upon the

tenant’s vacation or eviction, its duty to perform repairs at the unit,

its right to enter the unit upon the conditions specified in the lease,

and its right to show the unit to prospective tenants and other

interested parties. Moreover, the Adams parties did not introduce

evidence of “a pattern” that aunt maintained and repaired the unit

without notice to CAI or that CAI had stopped inspecting the unit.

See Nordin, 148 P.3d at 221.

¶ 88 In sum, Ms. Adams was a landowner for purposes of the Act

because CAI was “in possession” of the unit; Ms. Adams was CAI’s

“authorized agent” and the principal individual through whom CAI

performed its duties as property manager for the unit; and Ms.

Adams, in her capacity as CAI’s authorized agent, “manage[d],

superintend[ed], direct[ed], or overs[aw] repairs” at the unit, id. at

220-21. § 13-21-115(7)(b). In reaching this conclusion, we do not

hold that Ms. Adams was CAI’s alter ego. The General Assembly

intended that certain officers and agents of property owners,

40
managers, and similar entities could be deemed landowners under

the Act through their role as “authorized agent[s] or . . . person[s] in

possession of real property.” § 13-21-115(7)(b). This statutory

provision does not mean that, without more, these individuals can

also be held personally liable for the entity’s debts under an alter

ego theory. See Brightstar LLC v. Jordan, 2024 COA 39, ¶ 122, 552

P.3d 1133, 1157.

V. Attorney Fees

¶ 89 Because we agree with the Adams parties that the court erred

by providing the jury with an instruction containing the language of

the 2012 IFC, we decline the children’s request for an award of

attorney fees. Under section 13-17-102(2), a court may award

reasonable appellate fees in civil actions lacking substantial

justification. The Adams parties’ arguments do not lack substantial

justification.

VI. Disposition

¶ 90 The judgment is reversed, and the case is remanded to the

trial court for further proceedings consistent with this opinion.

JUDGE JOHNSON and JUDGE MOULTRIE concur.